Kongsberg WCC 600 Watch Call Panel | 373860 | 5.7" LCD Touchscreen | Unattended Engine Room | Engine Room Alarm Indication | Watch Duty Transfer | 8 Engineers On-Duty | 24VDC | K-Chief 600/700 | Class
1. Product Overview
The Kongsberg WCC 600 (part no. 373860) is a Watch Call Panel manufactured by Kongsberg Maritime AS of Norway, and is the core operator terminal in K-Chief 600/700 series marine automation systems and Unattended Machinery Space (UMS) systems, used for ship-wide indication of engine room alarms and acceptance/transfer of watch duty, as well as engineer watch management.
In unattended engine room operating mode, the engine room does not require personnel on duty 24 hours a day. Engine room equipment operating status and alarm information, after being acquired by the K-Chief automation system, need to be transmitted in real-time to the bridge, engineer duty cabins, and public areas, ensuring that duty personnel can promptly learn of alarms and take corresponding measures. The WCC 600 Watch Call Panel is precisely the key device undertaking this function. It presents engine room alarm information to duty personnel in an intuitive visual and audible manner, and provides an operation interface for watch duty transfer and acknowledgement.
The WCC 600 is equipped with a 5.7-inch LCD touchscreen, adopting a user-friendly and intuitive interface design, even ship personnel without professional training can easily operate it. The touchscreen supports alarm information display, menu navigation, parameter setting, watch duty operation, and other functions. When an alarm occurs in the system, the WCC 600 automatically triggers buzzer sound and visual indication (screen prompt and indicator light), and automatically switches to the Alarm Summary Page, presenting detailed alarm information to duty personnel, including alarm source, alarm time, alarm level, alarm description, etc. Alarms in the system can be grouped and configured according to customer requirements, facilitating classified management and quick location.
The WCC 600 supports multiple installation locations. According to different installation locations, its main functions also have different focuses:
Bridge Installation: The WCC 600 installed on the bridge mainly functions to indicate engine room alarms, as well as indicate and accept the transfer of engine room watch responsibility to and from the bridge. When the engine room is in unattended mode, bridge duty personnel monitor engine room alarm status through the WCC 600, and accept or transfer watch duty when needed.
Engineer Duty Cabin Installation: The WCC 600 installed in engineer duty cabins mainly functions to indicate engine room alarms in bridge control mode. When engineers are resting in the cabin, once an engine room alarm occurs, the WCC 600 wakes up the engineer through buzzer and screen prompt, enabling timely response.
Public Area Installation: The WCC 600 installed in public areas (such as mess room, corridor, changing room, etc.) is used to expand alarm coverage, ensuring that engineers can promptly learn of engine room alarm information regardless of their location on the ship.
The WCC 600 has comprehensive watch management functions, supporting indication and selection of two modes: "Attended Engine Room" and "Unattended Engine Room". The system supports watch management for up to 8 engineers, can display current duty personnel, duty time, duty handover, and other information. The panel provides "Acknowledged from Cabin" indication function. When an engineer acknowledges an alarm in the cabin, other panels will display that the alarm has been acknowledged, avoiding multiple personnel responding repeatedly.
In terms of electrical performance, the WCC 600 adopts 18-32V DC wide voltage power supply (nominal 24V DC), adapting to ship power grid voltage fluctuations, power consumption only 5W, low heat generation, suitable for long-term continuous operation. Operating temperature range is -15°C to +70°C, storage temperature -25°C to +70°C, maximum relative humidity 96% (non-condensing), can operate stably in various ship environments. Panel weight approximately 1.1kg, compact structure, suitable for flush mounting or wall mounting.
The WCC 600, as a standard component of K-Chief 700 and K-Safe systems, has obtained Bureau Veritas (BV) Type Approval, and is certified by major classification societies such as DNV-GL, ABS, LR, etc. Widely used in unattended engine room watch calling systems on various commercial ships, offshore platforms, special vessels. The product is genuine Kongsberg original, with a 12-month quality warranty.
2. Specifications
表格
| Parameter | Value |
|---|---|
| Brand | Kongsberg Maritime AS (Norway) |
| Model | WCC 600 |
| Part No. | 373860 |
| Product Type | Watch Call Panel |
| Applicable System | K-Chief 600/700 marine automation systems, Unattended Machinery Space (UMS) systems |
| Common Revision | Revision D1 (other revisions may exist) |
| Display | 5.7-inch LCD Touchscreen |
| Display Resolution | To be confirmed |
| Touchscreen Type | Resistive or capacitive (to be confirmed) |
| User Interface | Graphical user interface, menu navigation, alarm summary page |
| Alarm Indication | Buzzer sound + screen visual prompt + indicator lights |
| Alarm Summary | Automatically switches to alarm summary page on alarm, displays alarm source, time, level, description |
| Alarm Grouping | Supports grouped configuration according to customer specifications |
| Watch Duty Transfer | Supports acceptance and transfer of watch duty between bridge and engine room |
| Engine Room Mode | Supports Attended/Unattended Engine Room indication and selection |
| Duty Personnel Management | Supports up to 8 engineers on-duty management |
| Cabin Acknowledgement Indication | Supports "Acknowledged from Cabin" indication |
| Installation Locations | Bridge, engineer duty cabins, public areas |
| Supply Voltage | 18 - 32 V DC (nominal 24V DC) |
| Power Consumption | 5 W |
| Operating Temperature | -15°C ~ +70°C |
| Storage Temperature | -25°C ~ +70°C |
| Max Relative Humidity | 96% RH (non-condensing) |
| Protection Degree | To be confirmed (front panel reference IP54/IP65, rear IP20) |
| Communication Interface | To be confirmed (communicates with K-Chief system, reference CAN bus or Ethernet) |
| Communication Protocol | To be confirmed (K-Chief system proprietary protocol) |
| Buzzer | Built-in, triggered on alarm |
| Indicators | Power, communication, alarm and other status indicators (specific configuration to be confirmed) |
| Operation Method | Touchscreen operation + possible physical keys (to be confirmed) |
| Housing Material | Marine-grade corrosion-resistant material (specific material to be confirmed) |
| Color | To be confirmed (reference black or dark gray panel) |
| Dimensions | To be confirmed (reference standard flush panel size, subject to actual product) |
| Weight | Approximately 1.1 kg |
| Mounting Method | Flush Mount or Wall Mount |
| Cooling Method | Natural cooling (fanless) |
| Firmware Upgrade | Supports upgrade via system network or dedicated interface (to be confirmed) |
| Self-Diagnostic | To be confirmed (supports panel self-test and communication status monitoring) |
| Classification Society Certification | DNV-GL, ABS, LR, BV (as K-Chief system component) |
| EMC Standard | To be confirmed (reference IEC 60945 related EMC requirements) |
| Vibration & Shock | To be confirmed (meets marine environment requirements) |
| Official Documentation | WCC 600 Watch Call Panels technical document (No.381827), Outline Drawing (No.374548) |
| Country of Origin | To be confirmed (Norway or Kongsberg global manufacturing base) |
| HS Code | To be confirmed (reference 85311000 or 85437090, alarm panel/electrical equipment) |
| Stock Status | Order available |
| Warranty Period | 12 months |
3. Key Features
- Dedicated Watch Call Panel for Unattended Engine Room — The WCC 600 is a watch call panel specifically designed for Unattended Machinery Space (UMS) systems, is the standard operator terminal for K-Chief 600/700 automation systems, achieving ship-wide transmission of engine room alarm information and standardized management of watch duty, ensuring safe ship operation in unattended engine room mode.
- 5.7-inch LCD Touchscreen, Intuitive and Easy to Use — Equipped with a 5.7-inch LCD touchscreen, adopting graphical user interface and menu navigation design, user-friendly and intuitive, even ship personnel without professional training can easily operate. The touchscreen supports alarm information viewing, menu navigation, parameter setting, watch duty operation, and other functions, convenient and efficient operation.
- Automatic Alarm Summary and Audible-Visual Indication — When an alarm occurs in the system, the WCC 600 automatically triggers buzzer sound and visual indication (screen prompt and indicator lights), and automatically switches to the alarm summary page, presenting detailed alarm information to duty personnel, including alarm source, alarm time, alarm level, alarm description, etc., ensuring duty personnel learn alarm details at the first time.
- Watch Duty Acceptance and Transfer — Supports acceptance and transfer of watch duty between bridge and engine room. The panel can clearly indicate current watch duty ownership, and provides acceptance and transfer operation interface. Standardized watch duty management process ensures clear responsibility and clear handover in unattended engine room mode, complying with ship safety management regulations.
- Attended/Unattended Engine Room Mode Switching — Supports indication and selection of two operating modes: Attended Engine Room and Unattended Engine Room. Operators can switch modes according to actual operating conditions, the system automatically adjusts alarm strategy and watch management logic, adapting to different ship operating conditions.
- Up to 8 Engineers Watch Management — The system supports watch management for up to 8 engineers, can display current duty personnel, duty time, duty handover, and other information, 配合 watch scheduling function, achieving standardized management of engineer watch. Cabin acknowledgement indication function can display which engineer has acknowledged the alarm in the cabin, avoiding multiple personnel responding repeatedly.
- Multi-Location Installation, Ship-Wide Alarm Coverage — Supports installation in multiple locations such as bridge, engineer duty cabins, public areas, etc. According to installation location, automatically adjusts function focus, achieving ship-wide coverage of engine room alarm information. Whether duty personnel are on the bridge, resting in cabin, or in public areas, they can promptly learn of engine room alarm information, ensuring no alarm is missed.
- Low Power Wide Voltage, Marine-Grade Reliability — Adopts 18-32V DC wide voltage power supply (nominal 24V DC), adapting to ship power grid voltage fluctuations, power consumption only 5W, low heat generation, suitable for long-term continuous operation. Operating temperature -15°C to +70°C, humidity 96% RH non-condensing, natural cooling fanless design, no moving parts, high reliability, long life, adapting to various harsh ship environments.
- Alarm Grouping and Customized Configuration — Alarms in the system can be grouped and configured according to customer requirements, facilitating classified management and quick location by system, by area, by level. Panel interface and functions can be customized according to specific ship requirements, meeting personalized needs of different ship types and shipowners.
- Multiple Classification Society Certifications, Globally Applicable — As a standard component of K-Chief 700 and K-Safe systems, obtained Bureau Veritas (BV) Type Approval, and certified by major international classification societies such as DNV-GL, ABS (American Bureau of Shipping), LR (Lloyd's Register), etc. Products meet regulatory requirements of global classification societies, can be applied to ships and offshore platforms flying any flag, no additional certification required.
4. Typical Applications
- Unattended Engine Room (UMS) Watch Calling System: Standard watch calling system core terminal for various unattended engine room ships, achieving ship-wide indication of engine room alarms and watch duty management, ensuring safe ship operation in unattended engine room mode
- Bridge Engine Room Alarm Indication: WCC 600 installed on the bridge, real-time indicating engine room alarm status, bridge duty personnel can monitor engine room equipment operating conditions through the panel, accept or transfer engine room watch duty
- Engineer Cabin Alarm Call: WCC 600 installed in engineer duty cabins, indicating engine room alarms in bridge control mode, waking up resting engineers through buzzer and screen prompt, enabling timely response to alarms
- Public Area Alarm Coverage: WCC 600 installed in public areas such as mess room, corridor, changing room, recreation room, etc., expanding alarm coverage, ensuring engineers can promptly learn of engine room alarms anywhere on the ship
- Attended/Unattended Engine Room Mode Management: When the ship switches between attended and unattended engine room modes, the WCC 600 provides mode indication and selection interface, the system automatically adjusts alarm strategy and watch management logic
- Engineer Watch Scheduling Management: Cooperating with ship watch scheduling system, the WCC 600 displays current duty personnel, duty time, duty handover information, supports up to 8 engineers watch management, achieving watch standardization
- Watch Duty Transfer and Handover: When engine room watch duty is transferred between bridge and engine room, the WCC 600 provides acceptance and transfer operation interface, clearly indicating current responsibility ownership, ensuring standardized and traceable handover process
- Alarm Acknowledgement and Response Management: After an engineer acknowledges an alarm in the cabin, the WCC 600 displays "Acknowledged from Cabin" indication, other panels synchronously display that the alarm has been acknowledged, avoiding multiple personnel responding repeatedly, improving alarm handling efficiency
- Bulk Carrier Automation System: Watch calling terminal for K-Chief automation systems on bulk carriers, monitoring alarms of engine room equipment, ballast systems, cargo hold systems, etc.
- Tanker/Chemical Carrier/LNG Carrier Automation: Watch calling systems for unattended engine rooms on tankers, chemical carriers, LNG carriers and other liquid cargo ships, monitoring alarms of engine room, cargo oil systems, ballast systems, inert gas systems, etc.
- Container Ship Automation: Watch calling systems for unattended engine rooms on large container ships, ship-wide coverage of engine room alarms, 配合 massive engine room equipment monitoring requirements
- Offshore Platform Automation: Watch calling terminal for automation systems on offshore drilling platforms, production platforms, FPSO, FSRU and other offshore facilities, monitoring alarms of platform production equipment, utility systems, safety systems
- Special Vessel Automation: Watch calling systems for unattended engine rooms on research vessels, icebreakers, engineering vessels, naval auxiliary vessels, salvage vessels and other special ships, meeting watch management needs of special vessels
- New Shipbuilding System 配套: Supporting watch call panels for newly built ship K-Chief 600/700 automation systems and unattended engine room systems, configured quantity and installation positions according to system design
- Old System Upgrade and Retrofit: Watch call panel replacement and expansion when upgrading old ship unattended engine room systems to K-Chief systems, replacing old alarm indication panels
5. Model Explanation
Product Model: WCC 600
Part No.: 373860
Product Description: Watch Call Panel, for K-Chief 600/700 Marine Automation System and Unattended Machinery Space (UMS)
Model code breakdown:
- WCC: Abbreviation for Watch Call Cabin / Watch Call Controller
- 600: Series model code, corresponding to K-Chief 600 system series
Common Hardware Revisions:
表格
| Revision | Description |
|---|---|
| Revision D1 | Common hardware revision |
| Other revisions | Other revisions may exist, specific subject to actual product |
Official Documentation:
- WCC 600 Watch Call Panels technical document, Document No. 381827
- WCC 600 Outline Drawing, Drawing No. 374548, Rev.D, dated 02.07.2013
- Obtained Bureau Veritas (BV) Type Approval as a component of K-Chief 700 and K-Safe systems
- Manufacturer: Kongsberg Maritime AS, P.O. Box 483, NO-3601 Norway
Key Parameters Summary:
表格
| Parameter | Value |
|---|---|
| Type | Watch Call Panel |
| Applicable System | K-Chief 600/700, UMS |
| Display | 5.7" LCD Touchscreen |
| Power Supply | 18-32V DC (24V nominal) |
| Power Consumption | 5W |
| Operating Temperature | -15°C ~ +70°C |
| Humidity | 96% RH non-condensing |
| Weight | Approximately 1.1kg |
| Duty Personnel | Up to 8 engineers |
| Certification | DNV-GL, ABS, LR, BV |
Related Products (reference):
表格
| Model | Description |
|---|---|
| WCC 600 | This product, Watch Call Panel |
| K-Chief 600 | Kongsberg marine automation system (WCC 600 compatible) |
| K-Chief 700 | Kongsberg new generation marine automation system (WCC 600 compatible) |
| K-Safe | Kongsberg safety control system (WCC 600 as component) |
| INP 330951 | Input Panel (K-Chief system operator terminal) |
| ALC 344687 | Alarm and Command Panel (K-Chief system operator terminal) |
| RCU 502i/602 | Remote Control Unit (K-Chief system main controller) |
Important Note: Some materials may incorrectly describe the WCC 600 as other types of equipment. Please refer to "WCC 600 Watch Call Panel" clearly stated in Kongsberg official documentation.
Brand: Kongsberg Maritime AS, global leading marine automation and ocean technology company, headquartered in Norway
6. Installation & Usage Instructions
Pre-Installation Preparation:
- Confirm WCC 600 model and hardware revision match system requirements
- Confirm installation location (bridge, engineer cabin, public area) and mounting method (flush/wall)
- Prepare installation tools (screwdriver, wire stripper, crimping tool, etc.)
- Prepare communication cable and power cable
- Read K-Chief system watch call panel installation manual and system documentation
Installation Notes:
- Installation and wiring must be performed in de-energized state, ensure safety
- Wear anti-static wrist strap to avoid electrostatic damage to panel circuit
- Select appropriate installation location, ensure duty personnel can easily observe and operate
- For bridge installation, avoid affecting navigation visibility and operation of other equipment
- For cabin installation, install near bedside or position where can be woken up during sleep
- For public area installation, select locations where personnel frequently move, ensure alarm coverage
- For flush mounting, confirm opening size matches panel
- For wall mounting, confirm mounting bracket is secure, adapts to ship vibration
- Avoid installing near heat sources, direct sunlight locations, and severe vibration locations
- Communication cables use shielded twisted pair, routed separately from power cables
- Front panel has certain protection rating, but should still avoid long-term direct water spray and large amount of dust
- During installation, pay attention to protecting touchscreen surface, avoid scratches and impacts
Wiring Instructions:
- Power Wiring: 18-32V DC power supply connected to power terminals, pay attention to positive and negative polarity, nominal 24V DC
- Communication Wiring: Communication cable connects panel communication interface and K-Chief system network, pay attention to interface type and wiring standard
- Grounding Wiring: Panel protective grounding terminal reliably connected to grounding bar
- Buzzer: Built-in buzzer, no additional wiring required (if external alarm is needed, connect according to system wiring diagram)
- All wiring terminals should be tight and reliable, avoid virtual connections
- After wiring completion, check all wiring, confirm correct before power-on
Configuration & Commissioning:
- Confirm all wiring is correct and panel is installed in place
- Turn on 24V DC power, observe panel startup and touchscreen display
- After panel starts, confirm display is normal, touchscreen response is normal
- Confirm panel communication with K-Chief system is normal, system automatically recognizes panel
- Configure panel address, installation location, function parameters in system configuration software
- Configure alarm grouping: configure alarm grouping and display strategy according to ship system
- Configure duty personnel: input up to 8 engineer information, configure watch scheduling
- Test touchscreen: click each menu and button, confirm response normal
- Test alarm indication: simulate system alarm, confirm buzzer sounds, screen automatically switches to alarm summary page, indicator lights up
- Test watch duty transfer: test acceptance and transfer of watch duty between bridge and engine room panels
- Test attended/unattended engine room mode switching: switch mode, confirm system response correct
- Test cabin acknowledgement indication: acknowledge alarm on cabin panel, confirm other panels display "Acknowledged"
- Test panels at all installation locations, confirm functions normal
- Save system configuration, make configuration backup
- Record panel installation location, address, revision number, serial number, etc., include in system documentation
Usage Notes:
- Duty personnel should receive UMS system and WCC 600 operation training
- Operate touchscreen with clean hands or stylus, avoid oil, water contamination of screen
- Do not touch screen with sharp objects, prevent damaging touchscreen
- When cleaning screen surface, use soft dry cloth to wipe, do not use corrosive cleaners
- When alarming, should first view alarm summary page, confirm alarm source and level before taking corresponding measures
- Before transferring watch duty, should confirm engine room status, ensure transfer is safe
- Do not arbitrarily change system configuration and parameters, configuration modification should be performed by authorized personnel
- When panel fails, promptly notify maintenance personnel, do not disassemble by yourself
- In unattended engine room mode, duty personnel should keep WCC 600 panel within observable and operable range
Maintenance Recommendations:
- Regularly (recommended every 3-6 months) check panel operating status, touchscreen function, buzzer function
- Regularly clean touchscreen surface and panel housing, keep clean
- Regularly check wiring terminals for looseness, especially in high-vibration areas
- Regularly check communication cables and connectors are normal
- Regularly backup system configuration files
- Recommended to stock 1-2 WCC 600 panels as ship spare parts for quick replacement in case of failure
- Touchscreen is a vulnerable component, if touch insensitive, display abnormal, etc., can replace panel
- If buzzer sound becomes low or no sound, check buzzer settings or replace panel
- When panel fails, can quickly recover by replacing spare part, faulty panel sent for professional repair
- Keep installation location clean, dry, well-ventilated
- When upgrading K-Chief system software, confirm panel firmware compatibility, upgrade panel firmware if necessary
Safety Notes:
- Panel operates at safety voltage, but connected systems and equipment may involve high voltage, pay attention to high-voltage hazard of related equipment during maintenance
- Maintenance of panels involved in UMS safety systems must follow ship safety management regulations, notify captain and duty personnel if necessary, during maintenance personnel should be arranged to temporarily attend engine room
- Wait for panel to fully discharge after power-off before plugging/unplugging
- When replacing panel, first disconnect power and communication connections, then remove
- Discarded electronic panels should be disposed of per ship garbage management regulations and e-waste regulations
7. Why Choose Us
- Professional Procurement Channel, Quality Guaranteed — All products obtained through professional procurement channels, ensuring genuine Kongsberg original products, with product identification and quality documents, provides 12-month quality warranty. Appearance check, model confirmation, and function test performed before shipment, ensuring delivered products are intact, model-accurate, and functional.
- Worldwide Delivery — Supports DHL, FedEx, UPS and other international couriers. Can also ship via your designated freight forwarder to 200+ countries, can arrange ship port delivery. Panel products use shock-proof and moisture-proof professional packaging, ensuring transportation safety.
- Professional Technical Support — Provides selection consultation (confirming K-Chief system compatibility, hardware revision matching, installation location and quantity planning), installation guidance, system configuration support, watch management scheme recommendations, fault diagnosis, and spare part replacement suggestions, helping you correctly install and maintain ship watch calling systems.
- Flexible Procurement — Supports single panel procurement and bulk project orders, tiered pricing discounts with quantity. Can provide new shipbuilding project-specific quotations, ship spare part packages (WCC 600 + related panels + accessories combination), and annual spare part framework agreements.
- Pre-shipment Inspection — Appearance check, packaging verification, model confirmation, revision check, and power-on test (touchscreen test, buzzer test, indicator test, communication test) performed before shipment, ensuring delivered products have accurate configuration, normal functions, and are intact.
8. Frequently Asked Questions (FAQ)
Q1: What is this WCC 600? What is the difference from ordinary alarm panels?
A: The WCC 600 is a Watch Call Panel, which is a dedicated operator terminal for Kongsberg K-Chief 600/700 marine automation systems and Unattended Machinery Space (UMS) systems, mainly used for ship-wide indication of engine room alarms and watch duty management.
Difference from ordinary alarm panels:
表格
| Comparison Item | WCC 600 Watch Call Panel | Ordinary Alarm Panel |
|---|---|---|
| Display | 5.7" LCD touchscreen, graphical interface | Usually only indicators or simple digital tube |
| Alarm Information | Displays detailed info: source, time, level, description | Usually only alarm light, no detailed info |
| Alarm Summary | Automatically switches to alarm summary page on alarm | No this function |
| Watch Duty Management | Supports watch duty acceptance/transfer, attended/unattended mode | Usually no this function |
| Engineer Watch | Supports up to 8 engineers watch management | Usually no this function |
| Cabin Acknowledgement | Supports alarm acknowledged from cabin indication | Usually no this function |
| Operation Method | Touchscreen operation, menu navigation | Usually only simple keys |
| System Integration | Deeply integrated with K-Chief system, bidirectional communication | Usually only one-way alarm indication |
Simply put: An ordinary alarm panel can only tell you "there is an alarm", while the WCC 600 can tell you "what alarm, when, what level, how to handle", and can also manage watch duty and engineer watch. It is an intelligent operator terminal for unattended engine room systems.
Q2: Where can WCC 600 be installed? How many does a ship need?
A: The WCC 600 can be installed in the following locations:
- Bridge: Usually install 1-2, main function is to indicate engine room alarms, as well as accept/transfer engine room watch duty. The bridge is the main duty position in unattended engine room mode, must be equipped.
- Engineer Duty Cabins: Install 1 in each duty engineer's cabin, main function is to indicate engine room alarms in bridge control mode, waking up resting engineers through buzzer. Usually equip 2-4 (according to number of duty engineers).
- Public Areas: Mess room, corridor, changing room, recreation room and other areas where personnel frequently move, expanding alarm coverage. Equip 1-3 according to ship size.
- Engine Control Room: Operation position in attended engine room mode, can equip 1.
How many does a ship need?
- This depends on ship size, automation level, UMS configuration, and shipowner requirements
- Typical configuration reference:
- Small vessels (such as offshore supply vessels): Bridge 1 + Chief Engineer cabin 1 + 2nd Engineer cabin 1 = approx. 3
- Medium vessels (such as bulk carriers, container ships): Bridge 1-2 + 3-4 engineer cabins + 1-2 public areas = approx. 6-8
- Large vessels (such as LNG carriers, large tankers, offshore platforms): Bridge 2 + 4-8 engineer cabins + 2-3 public areas + ECR 1 = approx. 10-15
- Specific quantity should be determined according to K-Chief system design documentation and ship safety management requirements
- It is recommended that you provide ship type, engine room configuration, watch system, we can assist in planning configuration quantity and installation locations
Q3: Can the touchscreen and buzzer of WCC 600 be turned off or adjusted?
A: Yes, the WCC 600 usually supports the following adjustment functions (specific functions subject to system configuration):
Touchscreen:
- Screen brightness adjustable, adapts to different ambient light
- Screen saver function, can reduce brightness or black screen after long time no operation (automatically wakes up on alarm)
- Touchscreen calibration function, can calibrate if touch offset occurs
- Note: On alarm, screen automatically wakes up and switches to alarm summary page, cannot completely turn off alarm display
Buzzer:
- Buzzer volume adjustable, adapts to different ambient noise
- Buzzer muted after alarm acknowledgement (alarm light and screen prompt remain until alarm reset)
- Can set different alarm levels corresponding to different buzzer tones or rhythms
- Note: Buzzer for emergency alarms (such as fire, flooding, main engine failure) usually cannot be completely turned off, to ensure safety
- Cabin panel buzzer usually designed loud enough to wake sleeping engineers, not recommended to set too low
Other settings:
- Alarm group display configurable, can choose which groups of alarms to display
- Duty personnel information configurable
- Language setting (if system supports multi-language)
- All configuration modifications should be performed by authorized personnel, save configuration after modification
Recommendation: Bridge panel buzzer volume should be moderate, avoid affecting navigation watch; cabin panel buzzer volume should be loud enough, ensure can wake sleeping engineers; public area panel buzzer volume should adapt to ambient noise.
Q4: How to install this panel? Does it require professional personnel?
A: Installation of WCC 600 includes three steps: mechanical installation, wiring, and system configuration.
Mechanical installation:
- Supports Flush Mount and Wall Mount
- Flush mounting: Open hole on console or wall according to panel size, insert panel from front, fix with mounting bracket from rear
- Wall mounting: Fix panel on wall or console surface with mounting bracket
- During installation, pay attention to secure fixing, adapt to ship vibration
Wiring:
- Power cable: 18-32V DC power supply connected to power terminals, pay attention to positive and negative polarity
- Communication cable: Communication cable connects panel and K-Chief system network
- Grounding cable: Connect protective grounding
- All wiring tight and reliable
System configuration:
- After panel accesses system, need to add panel, configure address, set installation location and function parameters in K-Chief system configuration software
- Configure alarm grouping, duty personnel, watch scheduling, etc.
- Test all functions
Does it require professional personnel?
- Mechanical installation and wiring: Can be completed by ship electrician or automation technician, requires basic electrical installation knowledge
- System configuration and commissioning: Recommended to be completed by professional technical personnel familiar with K-Chief systems, because involves system configuration, alarm grouping, watch management settings, function testing, etc.
- If it is a simple spare part replacement (same model replacement), mechanical and wiring are relatively simple, but system configuration and function testing still recommended to be confirmed by professional personnel
- We provide installation guidance and technical support, can assist your technical personnel in completing installation and commissioning
Q5: Is this product in stock? What is the lead time? What is the price?
A: This model is currently in order available status, standard lead time 4-8 weeks (ordered through professional procurement channels or allocated from global inventory). The WCC 600 is a dedicated marine automation watch call panel, with limited stock inventory, usually requiring procurement to order or allocation from global inventory.
- Price: Specific price subject to our formal quotation, price depends on hardware revision, quantity, whether includes system configuration service, supply channel and other factors. Bulk procurement can enjoy tiered discounts.
- Expedited service: If you have urgent needs (such as ship failure in port, tight shipping schedule, PSC inspection deficiency rectification, UMS certification inspection), we can try to coordinate global stock inventory or expedited ordering, specific please contact our sales team.
- Please indicate required quantity, hardware revision, ship type, installation location, desired delivery time, and destination port when inquiring, we will do our best to coordinate the fastest delivery solution and optimal price.
Q6: How to judge and replace a faulty WCC 600? Does it need reconfiguration?
A: Fault judgment methods:
- Power failure: Panel no display, touchscreen off, buzzer silent → may be power failure, power cord loose, fuse blown, or panel internal power damage
- Communication failure: Panel has display but cannot receive alarms, system shows panel offline or communication interruption → may be communication cable failure, network switch port failure, panel communication interface damage, or system configuration issue
- Touchscreen failure: Display normal but touch no response, touch offset, partial area malfunction → may be touchscreen damage, touch calibration 失效,or touch controller failure
- Buzzer failure: On alarm, buzzer silent, sound low, or abnormal sound → may be buzzer setting issue, buzzer damage, or driver circuit failure
- Display failure: Screen black, garbled, abnormal display, brightness abnormal → may be display damage, backlight failure, or display controller failure
- System error: K-Chief system shows panel hardware failure, self-test failed → may be panel hardware failure or firmware corruption
- Intermittent failure: Panel occasionally freezes, restarts, alarm not responding → may be power instability, poor contact, overheating, or hardware aging
Replacement steps:
- Notify duty personnel and captain (if 涉及 UMS safety systems), explain that panel replacement will be performed
- During maintenance, personnel should be arranged to temporarily attend engine room (if replacing a key location panel)
- Disconnect panel power and communication connections
- Remove faulty panel (loosen mounting bracket, unplug cables)
- Install new panel in the same position, fix securely
- Restore power cable, communication cable, and grounding cable
- Turn on power, observe panel startup and touchscreen display
- Confirm panel communication with system is normal, system recognizes panel
- Test touchscreen: click each menu and button, confirm response normal
- Test buzzer: simulate alarm, confirm buzzer sounds normally
- Test alarm indication: simulate system alarm, confirm screen automatically switches to alarm summary page
- Test watch duty transfer and attended/unattended engine room mode switching
- If panel has address configuration, confirm address setting is correct
- Record replacement date, new panel serial number, revision number, include in system documentation
Regarding reconfiguration:
- If same model same revision replacement: Usually no reconfiguration required, panel automatically recognized after accessing system, original configuration automatically takes effect. But recommended to check system configuration, confirm panel address and functions are correct
- If different revision replacement: May need to update panel model and revision information in system configuration software, confirm function compatibility, upgrade system software if necessary
- If adding new panel (not in original system): Need to add panel, configure address, assign installation location, set alarm grouping and watch functions in system configuration software, this requires professional technical personnel
- Recommendation: After replacement, perform comprehensive function test, confirm touchscreen, buzzer, alarm indication, watch management and all other functions are normal. If unsure about configuration, recommended to consult professional technical personnel