Company Culture    Electrical    High & Low Voltage Electrical Equipment    Thermal Relays    ABB TA75DU-63M 1SAZ321201R2005 Thermal Overload Relay 45-63A

ABB TA75DU-63M 1SAZ321201R2005 Thermal Overload Relay 45-63A

Brand: ABB (Switzerland/Sweden)
Model: TA75DU-63M
Order Code: 1SAZ321201R2005
Setting Range: 45.0 — 63.0
online consultation

Product Details

I. Product Overview

The ABB TA75DU-63M is a TA75DU series thermal overload relay (Thermal Overload Relay) manufactured by Swiss ABB, adopting the bimetallic thermal tripping principle to provide reliable overload protection and phase failure protection for three-phase asynchronous motors. This relay has a current setting range of 45.0-63.0A, 3-pole (3P) design, trip class Class 10A, suitable for three-phase motor circuits with rated current not exceeding 63A.

The TA75DU series is ABB's classic economical electromechanical thermal overload relay series, using bimetallic thermal elements. The heat generated by the motor current causes the bimetallic strips to bend and deform, driving the tripping mechanism to operate for overload protection. This series features temperature compensation, maintaining stable tripping characteristics under ambient temperature variations; and phase failure protection (achieved through the differential mechanism), preventing motor burnout due to phase loss operation. The TA75DU series complies with IEC/EN 60947-4-1 and other standards, has passed multiple international certifications, and is widely used in industrial motor starting and protection circuits.

The TA75DU-63M can be directly mounted on ABB A series larger contactors (such as A50, A63, A75, etc.) to form a motor starter, or panel-mounted via an independent mounting base (terminal block). The relay features 1 NC trip contact (95-96) and 1 NO signal contact (97-98), suitable for control circuit interlocking and fault signal indication. The reset mode can be selected between automatic or manual reset, and features a trip-free mechanism to ensure reliable operation of the tripping mechanism under all conditions. Additionally, the relay has a STOP button function and a test function for convenient on-site operation and functional verification. The product has a main circuit rated operating voltage of 690V AC, rated insulation voltage 690V, rated impulse withstand voltage 6kV, weight approximately 335g, reference dimensions 54mm × 90mm × 111mm.

II. Specifications

表格

Parameter Value
Brand ABB
Series TA75DU
Model TA75DU-63M
Order Code 1SAZ321201R2005 (China mall code 10139498)
Product Type Thermal Overload Relay
Operating Principle Bimetallic thermal tripping
Number of Poles 3P
Current Setting Range 45.0 ~ 63.0 A
Rated Operational Current (Ie) 63 A
Rated Operating Voltage (Ue) Main circuit 690V AC / 440V DC
Auxiliary Circuit Voltage 500V AC / 440V DC
Rated Insulation Voltage (Ui) 690 V
Rated Impulse Withstand Voltage (Uimp) 6 kV
Rated Frequency (f) Main circuit 50/60Hz, DC; Auxiliary circuit 50/60Hz, DC
Trip Class Class 10A
Number of Protected Poles 3
Auxiliary Contacts 1NC (trip contact 95-96) + 1NO (signal contact 97-98)
Conventional Thermal Current of Auxiliary Contacts (Ith) NC 10A, NO 6A
Phase Failure Protection Yes (differential type)
Temperature Compensation Yes
Reset Mode Automatic/manual selectable
Trip-free Mechanism Yes
STOP Function Yes (can be used as stop button)
Test Function Yes
Trip Indication Yes
Mounting Direct mounting on A series larger contactors or independent mounting (base)
Compatible Contactors ABB A50, A63, A75, etc. (contact via email for confirmation)
Reference Dimensions 54mm × 90mm × 111mm
Weight Approx. 335 g
Applicable Standards IEC/EN 60947-4-1
Approvals CE, CCC, etc. (contact via email for confirmation)
Country of Origin Contact via email for confirmation (China/Bulgaria, etc.)

III. Product Features

  • ABB quality, TA75DU series classic economical thermal overload relay, reliable performance
  • Bimetallic thermal tripping principle, accurate and reliable overload protection
  • 3-pole (3P) design, suitable for three-phase motor circuits
  • Current setting range 45.0-63.0A, dial adjustment, easy to set
  • Trip class Class 10A, trips within 10 seconds (7.2×Ie), suitable for general industrial motor starting
  • Differential phase failure protection, preventing motor burnout from phase loss
  • Temperature compensation, maintaining stable tripping characteristics
  • 1NC trip contact + 1NO signal contact, complete control interlocking and fault indication
  • Automatic/manual reset selectable, adapting to different application requirements
  • Trip-free mechanism, ensuring reliable tripping under all conditions
  • STOP button function, can also be used as a stop button
  • Test function, convenient for on-site functional verification
  • Clear trip indication, easy fault diagnosis
  • Direct mounting on ABB A series larger contactors to form motor starters, easy installation
  • Also supports independent panel mounting, flexible for various cabinet layouts
  • Rated operating voltage 690V AC, rated insulation voltage 690V, rated impulse withstand voltage 6kV
  • IEC/EN 60947-4-1 compliant, multiple international certifications
  • Widely used in industrial motor starting and protection circuits

IV. Typical Applications

  • Overload protection for three-phase asynchronous motors
  • Phase failure (phase loss) protection for motors
  • Combination with ABB A series contactors to form motor starters (direct-on-line starting)
  • Motor protection for medium-to-large power industrial pumps, fans, compressors
  • Motor protection for conveyors, mixers, crushers, mills and other machinery
  • Motor protection for large-power HVAC systems
  • Motor protection for air compressors and refrigeration compressors
  • Motor protection for large machine tools and automation equipment
  • Motor protection for large-power building water supply and drainage systems
  • Motor protection circuits in metallurgy, chemical, mining, power industries

V. Model Description

TA75DU-63M is the complete model number for the ABB TA75DU series thermal overload relay. Where:

  • TA: ABB thermal overload relay series code (Thermal relay, bimetallic type)
  • 75: Series frame size/design code
  • DU: Differential Unit, featuring phase failure protection
  • 63: Upper limit of current setting range (63A, setting range 45.0-63.0A)
  • M: Version/config suffix (specific meaning, contact via email for confirmation)

The ABB TA75DU series thermal overload relay current setting ranges cover 45-80A. Common specifications include: TA75DU-63 (45-63A, order code 1SAZ321201R1005), TA75DU-80 (60-80A, order code 1SAZ321201R1006), etc. TA75DU-63M corresponds to the 45.0-63.0A specification, suitable for motor loads with rated current of 45-63A.

The TA75DU series can be directly mounted on ABB A series larger contactors, or panel-mounted via independent mounting bases. To confirm the detailed configuration of this model (wiring capacity, independent mounting base model, compatible contactor selection, auxiliary contact electrical parameters, etc.), please contact via email for confirmation. We will provide detailed technical documentation and selection support.

VI. Why Choose Us

  • Professional channel supply, comprehensive model coverage across multiple brands of industrial spare parts
  • Strict quality inspection process ensuring reliable product quality
  • Professional engineering team providing technical support and selection consultation
  • Quick response, efficient logistics, orders accepted
  • Quality assurance, worry-free after-sales service

VII. FAQ

Q1: What is the current setting range of TA75DU-63M?

A: According to the ABB official datasheet, the current setting range of TA75DU-63M is 45.0-63.0A, with rated operational current (Ie) of 63A. This specification is suitable for three-phase motors with rated current of approximately 45-63A (corresponding to approximately 22-30kW motors at 380V). The current setting value should be adjusted according to the motor nameplate rated current, typically set at 1.0-1.05 times the motor rated current. It is recommended that selection be performed by professional electrical engineers.

Q2: What does Class 10A trip class mean?

A: The trip class indicates the maximum tripping time of the thermal overload relay at 7.2 times the setting current. Class 10A means that at 7.2×Ie current, the relay trips within 10 seconds (actually 2-10 seconds). This is the standard trip class of the ABB TA25DU/TA42DU/TA75DU series, suitable for general industrial motor starting (applications where starting time does not exceed 10 seconds). For motors with heavy starting (longer starting time), thermal overload relays with Class 20 or Class 30 should be selected.

Q3: What is the difference between the TA75DU series and the TA42DU series?

A: Both TA75DU and TA42DU are ABB TA series bimetallic thermal overload relays. The main differences are the current specifications and compatible contactors: the TA42DU series covers setting ranges of 18-42A, compatible with A30, A40, BC30 contactors; the TA75DU series covers setting ranges of 45-80A with larger current specifications, suitable for larger power motors, compatible with larger contactors such as A50, A63, A75 (specific matching models, contact via email for confirmation). Selection is determined by the motor rated current and the matching contactor specification.

Q4: How to use this relay with a contactor?

A: TA75DU-63M can be directly plugged and mounted on ABB A series larger contactors to form a compact motor starter, without additional wiring (main circuit is directly connected through the contactor terminals). It can also be panel-mounted via an independent mounting base, with the main circuit wired from the base terminals. The auxiliary contacts (95-96 NC, 97-98 NO) are connected to the control circuit for overload interlocking and fault signal indication. For specific mounting methods, base models and wiring diagrams, please contact via email for confirmation. We will provide detailed documentation.