Products

Classification

Company Culture    Electrical    High & Low Voltage Electrical Equipment    Soft Starters    Schneider ATS48C79Q Altistart 48 Soft Starter 675A

Schneider ATS48C79Q Altistart 48 Soft Starter 675A

Schneider ATS48C79Q Altistart 48 soft starter, Schneider Electric ATS48 series, line rating 675A, control voltage 220V, supply 230~415V, heavy duty 220~355kW/standard 400~630kW, 3-phase, TCS torque control, optional external bypass, used for soft starting and soft stopping of asynchronous motors, smooth starting avoiding mechanical stress, widely used in industrial drive systems.
online consultation

Product Details

I. Product Overview

The Schneider ATS48C79Q is a soft starter from the Altistart 48 series manufactured by Schneider Electric of France, model ATS48C79Q. This soft starter has a line rating of 675A, control voltage of 220V, supply voltage 230~415V, suitable for 220~355kW in heavy duty and 400~630kW in standard duty three-phase asynchronous motors, used for soft starting and soft stopping, achieving smooth motor start, reducing starting current and avoiding mechanical shock.

The Altistart 48 (ATS48) is Schneider Electric's premium soft starter series, designed for heavy industry and pump applications, covering 4~1200kW. This series features TCS (Torque Control System), achieving smooth start/stop via both voltage and torque control, supporting standard and heavy duty applications. The ATS48C79Q has utilization category AC-53A, supports optional external bypass, and provides comprehensive motor protection.

The ATS48C79Q is a three-phase application with protection rating IP00. This soft starter can be connected in the motor supply line (inline) or in the motor delta (inside delta), with inside delta connection supporting up to 630kW. Communication is Modbus (RS485, RJ45, baud rate 4800/9600/19200bps). It supports 5 logic inputs (including PTC probe 750Ω), 2 logic outputs and 3 relay outputs (fault, end of start, motor energized), with analog current output 0-20mA/4-20mA. Dimensions 770×315×890mm, net weight 115kg. It is widely used in pumps, fans, compressors and other applications.

II. Specifications

表格

Parameter Value
Brand Schneider Electric (France)
Model ATS48C79Q
Product Type Soft Starter
Series Altistart 48 (ATS48)
Line Rating (Standard/Heavy Duty) 675 A
Inside Delta Rating 1368 A
Control Voltage 220 V (50/60Hz)
Supply Voltage 230~415 V (-15%~+10%)
Motor Power Heavy duty: 230V/220kW, 400V/355kW; Standard: 400V/400kW; inside delta up to 630kW
Phases 3-phase
Utilization Category AC-53A
Start Control TCS Torque Control System (current limited to 5 In)
Bypass External bypass (optional)
Protection Rating IP00
Power Dissipation 2073W (heavy duty) / 2537W (standard)
Logic Inputs 5 (Stop, Run, LI3, LI4), PTC probe 750Ω supported
Logic Outputs 2 (0V common, configurable)
Relay Outputs 3 (fault NO, end of start NO, motor energized NO)
Analog Output Current output 0-20mA / 4-20mA
Communication Modbus (RS485, RJ45, 4800/9600/19200bps)
Supply Frequency 50/60Hz (-5%~+5%)
Inrush Current 0.4~1.3 Icl (adjustable)
Cooling Method Forced convection
Operating Temperature -10~40°C (without derating); 40~60°C (2%/°C derating)
Storage Temperature -25~70°C
Humidity 0~95% (non-condensing)
Operating Altitude ≤1000m (no derating); >1000~2000m (2.2%/100m derating)
Mounting Position Vertical ±10°
Noise Level 60 dB
Pollution Degree Level 3 (IEC 60664-1)
Dimensions 770 (W) × 315 (D) × 890 (H) mm
Net Weight 115 kg
Protection Functions Phase loss, motor thermal, starter thermal
Standard IEC 60947-4-2
Approvals CCC, CSA, C-Tick, DNV, GOST, NOM 117, SEPRO, TCF, UL, CE
Applicable Motor Three-phase squirrel-cage asynchronous motor
Typical Applications Heavy industry, pumps, fans, compressors
Manufacturer Schneider Electric (France)

III. Product Features

  • Schneider Altistart 48 soft starter
  • Model ATS48C79Q, line rating 675A
  • Control voltage 220V, supply 230~415V
  • Suitable for 220~630kW motors
  • TCS torque control system, smooth start/stop
  • Supports standard and heavy duty applications
  • External bypass design (optional)
  • Pump soft stop function, avoids water hammer
  • Avoids mechanical stress, extends equipment life
  • Reduces starting current, minimizes grid shock
  • Rich IO interfaces with Modbus communication
  • Comprehensive motor protection
  • Suitable for heavy industry applications

IV. Typical Applications

  • Water pump soft start and soft stop control
  • Fan soft starting
  • Conveyor drives
  • Compressor soft starting
  • Crushers and mixers
  • Conveying equipment
  • Heavy industrial drives
  • Three-phase asynchronous motor start control

V. Model Description

The ATS48C79Q fields are explained as follows:

  • ATS48: Schneider Altistart 48 soft starter series
  • C: Supply voltage code (230~415V)
  • 79: Model code (line rating 675A)
  • Q: Control voltage code (220V)

Note: This soft starter supports both inline connection and motor delta connection, with external bypass optional. To confirm bypass contactor, control voltage, terminal configuration and other details, please contact via email for confirmation. We will provide technical documentation and selection support.

VI. Why Choose Us

  • Professional channel supply, comprehensive model coverage across multiple brands of industrial spare parts
  • Strict quality inspection process ensuring reliable product quality
  • Professional engineering team providing technical support and selection consultation
  • Quick response, efficient logistics, orders accepted
  • Quality assurance, worry-free after-sales service

VII. FAQ

Q1: What is ATS48C79Q?

A: ATS48C79Q is a Schneider Altistart 48 series soft starter, line rating 675A, control voltage 220V, suitable for 220~630kW three-phase asynchronous motors.

Q2: What are the key parameters of this soft starter?

A: Line rating 675A, control voltage 220V, supply 230~415V, heavy duty 220~355kW / standard 400~630kW, 3-phase, IP00, TCS torque control, Modbus communication, net weight 115kg.

Q3: What protection functions does this soft starter have?

A: It has phase loss protection, motor thermal protection and starter thermal protection, supporting PTC motor temperature probe input.

Q4: How to confirm this soft starter's compatibility with the existing motor?

A: Please provide the existing motor power, rated voltage and rated current, contact via email, and we will assist in confirming compatibility and provide technical documentation.