GE Fanuc IC200DBI001 VersaMax DeviceNet Network Interface Unit (Slave NIU)
1. Product Overview
The IC200DBI001 is the DeviceNet Network Interface Unit (NIU) in the GE Fanuc (now Emerson Automation Solutions) VersaMax distributed I/O system. It is a DeviceNet slave (Group 2 Only Server). Installed in slot 0 of a VersaMax I/O station, it bridges the local I/O bus to the DeviceNet network: uplink via a 5-pin DeviceNet connector to a DeviceNet master (Scanner), downlink managing up to 8 VersaMax discrete/analog I/O modules per station.
DeviceNet supports multimaster, peer-to-peer and master/slave communication structures with broadcasting. Each NIU station occupies a unique node address (0–63) on the bus; node address and baud rate (125/250/500 Kbps) are set via rotary switches on top of the module. Data exchange supports cyclic I/O messaging (Change-Of-State and Polling) and acyclic explicit messaging.
A single DeviceNet network connects up to 64 nodes without bridging or routing. The NIU handles up to 128 bytes of input and 128 bytes of output data per scan.
2. Specifications
表格
| Item | Specification |
|---|---|
| Manufacturer | GE Fanuc / Emerson Automation Solutions / GE Automation and Controls |
| Series | VersaMax (distributed I/O) |
| Catalog number | IC200DBI001 |
| Product type | DeviceNet Network Interface Unit (NIU), DeviceNet slave |
| Slave type | Group 2 Only Server |
| Protocol | DeviceNet (CAN physical layer) |
| Network topology | Multimaster, peer-to-peer, master/slave with broadcasting |
| Max nodes per network | 64 (without bridge/router) |
| I/O modules per station | Up to 8 VersaMax I/O modules |
| Network data capacity | 128 bytes input / 128 bytes output per scan |
| I/O exchange types | Change-Of-State (COS), Polling |
| Messaging types | Cyclic I/O messaging + acyclic explicit messaging |
| Baud rates | 125 Kbps / 250 Kbps / 500 Kbps (switch-selected) |
| Max bus length | 500 m @125Kbps; 250 m @250Kbps; 100 m @500Kbps |
| Node address range | 0–63 (rotary switches) |
| Network connector | 5-pin open-style DeviceNet (threaded) connector |
| Backplane current draw | 5V DC: 160mA; 3.3V DC: 10mA |
| Power supply | Via VersaMax backplane; station requires a VersaMax power supply module |
| LED indicators | Yes (power, network status, module status) |
| Mounting position | Slot 0 (leftmost) of VersaMax carrier |
| Mounting | DIN rail or panel (with VersaMax carrier) |
| Operating temperature | −20 to +70 °C (typical VersaMax rating) |
| Compatible masters | Any DeviceNet Scanner master (PLC / PC interface card) |
Per GE Fanuc VersaMax Modules, Power Supplies, and Carriers User's Manual GFK-1504K and the DeviceNet NIU documentation. All nodes on the same DeviceNet network must use the same baud rate; node addresses must be unique. The I/O station requires a VersaMax power supply module.
5. Model Information
- Catalog number (ordering number): IC200DBI001
- Product description: GE Fanuc VersaMax DeviceNet Network Interface Unit (NIU), DeviceNet slave, installed in slot 0 of the VersaMax I/O station.
- Official catalog description: DeviceNet Network Interface Unit (IC200DBI001) is a DeviceNet slave module. DeviceNet supports a variety of communication structures including peer to peer, multimaster and master/slave with broadcasting capabilities. Up to 64 nodes can be connected to a DeviceNet network without bridging or routing.
- Material number note: IC200DBI001 is the official GE Fanuc / Emerson ordering number; "DBI" denotes DeviceNet Bus Interface. If you have questions on node address setting, baud rate selection or compatibility with a specific DeviceNet master, please contact us by email.
- Series features:
- DeviceNet slave NIU bridging local VersaMax I/O stations to the DeviceNet industrial network
- Three selectable baud rates 125/250/500 Kbps via top switches
- Up to 8 I/O modules per station, 128 bytes input / 128 bytes output
- Supports Change-Of-State and Polling I/O data exchange
- Standard 5-pin DeviceNet connector, node address 0–63 selectable
- Compact, installs in slot 0 of the VersaMax carrier
- LED status indicators for field diagnostics
- Related products in series: IC200EBI001 (Ethernet NIU), IC200PBI001 (Profibus-DP NIU), IC200GBI001 (Genius NIU), IC200PNS001 (PROFINET Scanner)
- Matching products: VersaMax I/O carriers (IC200CHS series), VersaMax power supplies (IC200PWR series), VersaMax discrete/analog I/O modules, DeviceNet trunk/drop cables and connectors, DeviceNet master Scanner
- Official documents: GE Fanuc VersaMax Modules, Power Supplies, and Carriers User's Manual GFK-1504K; DeviceNet Network Interface Unit User's Manual
6. Why Choose Us
- Exact model match: We verify supply against your full catalog number IC200DBI001, distinguishing DBI (DeviceNet) from EBI (Ethernet), PBI (Profibus), GBI (Genius) and other NIUs to avoid wrong shipment.
- Authorized channel supply: GE Fanuc / Emerson VersaMax modules supplied through regular channels, with product documentation available on request.
- Selection support: We help confirm baud rate, node address, I/O module count vs. data capacity and configuration matching with the DeviceNet master Scanner.
- Delivery & after-sales: Quotation, lead-time confirmation and order follow-up provided; for any parameter questions or alternative options, please contact us by email.
7. FAQ
Q1: What is the IC200DBI001?
A: The IC200DBI001 is the VersaMax DeviceNet Network Interface Unit (NIU), a DeviceNet slave that bridges a local VersaMax I/O station (up to 8 I/O modules) to the DeviceNet network, remotely read/written by a DeviceNet master Scanner. It provides no I/O points itself and must be paired with discrete/analog I/O modules.
Q2: What baud rates are supported? What is the maximum cable length?
A: 125 Kbps, 250 Kbps and 500 Kbps, selected by top switches. Approx. max bus length: 500 m at 125K, 250 m at 250K, 100 m at 500K. All nodes on the same network must use the same baud rate.
Q3: How many I/O modules can one station support?
A: Each IC200DBI001 NIU station supports up to 8 VersaMax I/O modules, with 128 bytes input and 128 bytes output data capacity. Actual I/O points depend on module density.
Q4: How is the node address set? Which addresses are allowed?
A: Node address range is 0–63, set via rotary switches on top of the module. Each node must have a unique address on the same DeviceNet network.
Q5: Does it require external power?
A: The NIU draws backplane power (5V/160mA, 3.3V/10mA), but the I/O station must have a VersaMax power supply module (e.g. IC200PWR series) to power the I/O modules and NIU. DeviceNet bus power is supplied separately by the network trunk.
Q6: How does it differ from other VersaMax NIUs?
A: IC200DBI001 is the DeviceNet interface; other NIUs include IC200EBI001 (Ethernet TCP/IP), IC200PBI001 (Profibus-DP), IC200GBI001 (Genius) and IC200PNS001 (PROFINET). Choose the one matching the network supported by your upper-level master/controller. Please email us to confirm compatibility.