The 140-MN-2500 is a manual motor starter and protector, Bulletin 140-MN series 3-pole device, thermal overload setting range 20 to 25 A with fixed magnetic trip at 275 A, rated ultimate breaking capacity 100 kA at 400/415 V, high current-limiting capability with short-circuit trip indication, can form a combination starter with a 100-C30 contactor, suitable for overload and short-circuit protection and manual switching of three-phase motors.
online consultation

Product Details

I. Product Overview

The 140-MN-2500 is a 3-pole manual motor starter and protector of the Bulletin 140-MN (KTA 3-25) series, with a thermal overload setting range of 20 to 25 A.

The device uses an adjustable thermal overload release plus a fixed-setting magnetic release: the instantaneous magnetic trip current is fixed at 11 times the highest thermal overload setting, which is 275 A for this model. The circuit breaker offers high making and current-limiting capability with a rated ultimate breaking capacity of 100 kA at 400/415 V, and provides short-circuit trip indication. Operated by a manual rotary handle, it provides switching, overload protection and short-circuit protection for motor circuits, and can form a combination motor starter together with a 100-C30 contactor.

II. Specifications

表格

Parameter Value
Model 140-MN-2500
Series Bulletin 140-MN (KTA 3-25)
Product Type Manual motor starter / motor protection circuit breaker (thermal-magnetic)
Poles 3
Thermal Overload Setting Range 20.00 to 25.00 A
Magnetic Trip Setting Fixed, 275 A (11 times the highest thermal overload setting)
Rated Ultimate Breaking Capacity Icu 100 kA at 400/415 V
Rated Service Breaking Capacity Ics 100 kA at 400/415 V
Applicable Motor (AC-3, 400/415 V) 11 kW / 23 A
Trip Indication Short-circuit trip indication
Operation Manual rotary handle
Matching Contactor 100-C30 (combination starter, IAC-3 30 kA)
Matching Current Limiter 140-CL2
Mounting Screw terminals, DIN rail/panel mounting, compact busbar and side-mounted accessories supported
Standards IEC 60947-2, IEC 60947-4-1

V. Model Description

The 140-MN-2500 belongs to the Bulletin 140-MN series (equivalent to Sprecher+Schuh KTA 3-25-25A); the suffix 2500 denotes a thermal overload setting range of 20 to 25 A. The replacement model listed in the official 140 product transition guide is 140M-C2E-C25 (setting range 18 to 25 A).

VI. Why Choose Us

  • Professional channel supply, comprehensive model coverage across multiple brands of low-voltage apparatus and motor control components
  • Strict quality inspection process ensuring reliable product quality
  • Professional engineering team providing technical support and selection consultation
  • Quick response, efficient logistics, orders accepted
  • Quality assurance, worry-free after-sales service

VII. FAQ

Q1: What is the 140-MN-2500?

A: A Bulletin 140-MN series 3-pole manual motor starter and protector with a thermal overload setting range of 20 to 25 A.

Q2: What is the magnetic trip current?

A: Fixed at 275 A, i.e. 11 times the highest thermal overload setting; at lower settings the multiple is correspondingly higher.

Q3: What is the breaking capacity of this model?

A: Both rated ultimate and rated service breaking capacity are 100 kA at 400/415 V.

Q4: How to confirm compatibility with my circuit?

A: Verify that the motor rated current falls within the 20 to 25 A setting range, check circuit voltage and breaking capacity requirements, and confirm a 100-C30 contactor with a 140-CL2 current limiter where required.