Allen-Bradley 140-MN-2500 Manual Motor Starter (20-25 A, 3-Pole)
I. Product Overview
The 140-MN-2500 is a 3-pole manual motor starter and protector of the Bulletin 140-MN (KTA 3-25) series, with a thermal overload setting range of 20 to 25 A.
The device uses an adjustable thermal overload release plus a fixed-setting magnetic release: the instantaneous magnetic trip current is fixed at 11 times the highest thermal overload setting, which is 275 A for this model. The circuit breaker offers high making and current-limiting capability with a rated ultimate breaking capacity of 100 kA at 400/415 V, and provides short-circuit trip indication. Operated by a manual rotary handle, it provides switching, overload protection and short-circuit protection for motor circuits, and can form a combination motor starter together with a 100-C30 contactor.
II. Specifications
表格
| Parameter | Value |
|---|---|
| Model | 140-MN-2500 |
| Series | Bulletin 140-MN (KTA 3-25) |
| Product Type | Manual motor starter / motor protection circuit breaker (thermal-magnetic) |
| Poles | 3 |
| Thermal Overload Setting Range | 20.00 to 25.00 A |
| Magnetic Trip Setting | Fixed, 275 A (11 times the highest thermal overload setting) |
| Rated Ultimate Breaking Capacity Icu | 100 kA at 400/415 V |
| Rated Service Breaking Capacity Ics | 100 kA at 400/415 V |
| Applicable Motor (AC-3, 400/415 V) | 11 kW / 23 A |
| Trip Indication | Short-circuit trip indication |
| Operation | Manual rotary handle |
| Matching Contactor | 100-C30 (combination starter, IAC-3 30 kA) |
| Matching Current Limiter | 140-CL2 |
| Mounting | Screw terminals, DIN rail/panel mounting, compact busbar and side-mounted accessories supported |
| Standards | IEC 60947-2, IEC 60947-4-1 |
V. Model Description
The 140-MN-2500 belongs to the Bulletin 140-MN series (equivalent to Sprecher+Schuh KTA 3-25-25A); the suffix 2500 denotes a thermal overload setting range of 20 to 25 A. The replacement model listed in the official 140 product transition guide is 140M-C2E-C25 (setting range 18 to 25 A).
VI. Why Choose Us
- Professional channel supply, comprehensive model coverage across multiple brands of low-voltage apparatus and motor control components
- Strict quality inspection process ensuring reliable product quality
- Professional engineering team providing technical support and selection consultation
- Quick response, efficient logistics, orders accepted
- Quality assurance, worry-free after-sales service
VII. FAQ
Q1: What is the 140-MN-2500?
A: A Bulletin 140-MN series 3-pole manual motor starter and protector with a thermal overload setting range of 20 to 25 A.
Q2: What is the magnetic trip current?
A: Fixed at 275 A, i.e. 11 times the highest thermal overload setting; at lower settings the multiple is correspondingly higher.
Q3: What is the breaking capacity of this model?
A: Both rated ultimate and rated service breaking capacity are 100 kA at 400/415 V.
Q4: How to confirm compatibility with my circuit?
A: Verify that the motor rated current falls within the 20 to 25 A setting range, check circuit voltage and breaking capacity requirements, and confirm a 100-C30 contactor with a 140-CL2 current limiter where required.