Products

넳 넲

Classification

Company Culture  ꄲ  Electrical  ꄲ  Electrical Meters  ꄲ  Eaton PFIM-100/2/01 Residual Current Circuit Breaker (100 A, 2P, 100 mA, Type AC)
ꁆ ꁇ

Eaton PFIM-100/2/01 Residual Current Circuit Breaker (100 A, 2P, 100 mA, Type AC)

The PFIM-100/2/01 is a 2-pole residual current circuit breaker of the xPole series, rated current 100 A, rated residual operating current 100 mA, Type AC (AC sensitive), conforming to IEC/EN 61008, rated short-circuit strength 10 kA and rated insulation voltage 440 V, 35 mm width occupying 2 modules, twin-purpose lift/open-mouthed terminals for conductors up to 35 mm², quick mounting on 35 mm DIN rail, for fault current protection and additional personal protection in distribution circuits.
online consultation

Product Details

I. Product Overview

The PFIM-100/2/01 is a 2-pole residual current circuit breaker (RCCB) of the xPole PFIM series, with a rated current of 100 A, a rated residual operating current of 100 mA, and Type AC sensitivity (AC sensitive, pulse-current sensitive), with instantaneous non-delayed tripping.

The device conforms to IEC/EN 61008, with a rated short-circuit strength of 10 kA, rated insulation voltage of 440 V and rated impulse withstand voltage of 4 kV. Tripping is line-voltage independent, making it suitable for fault current/residual current protection and additional protection; the supply may be connected to either side and the device functions irrespective of mounting position. The housing is gray (RAL 7035) with a red/green real contact position indicator, twin-purpose lift/open-mouthed terminals, and supports standard busbar connection as well as subsequent mounting of auxiliary and tripping signal switches.

II. Specifications

表格

Parameter Value
Model PFIM-100/2/01
Series xPole PFIM
Product Type Residual current circuit breaker (RCCB), Type AC
Poles 2P
Rated Current In 100 A
Rated Residual Operating Current IΔn 100 mA
Sensitivity AC sensitive (Type AC, pulse-current sensitive)
Tripping Characteristic Instantaneous, non-delayed
Rated Operational Voltage Ue 230 V AC (2-pole)
Rated Frequency 50 Hz
Rated Insulation Voltage Ui 440 V
Rated Impulse Withstand Voltage Uimp 4 kV (1.2/50 μs)
Rated Short-circuit Strength 10 kA
Rated Making and Breaking Capacity Im 1000 A (In = 100 A)
Maximum Back-up Fuse 100 A gG/gL
Electrical Endurance ≥4000 switching operations
Mechanical Endurance ≥20000 operations
Dimensions 80 mm H × 76 mm D × 35 mm W (2 modules)
Mounting 35 mm DIN rail (IEC/EN 60715), quick fastening with 2 lock-in positions
Terminals Twin-purpose lift/open-mouthed, top and bottom; single wire 1.5 to 35 mm², multi-wire 2 × 16 mm²; torque 2 to 2.4 N·m, M5 screws
Test Button Voltage Range 196 to 264 V AC (2-pole)
Degree of Protection IP40 (built-in); IP54 in moisture-proof enclosure
Ambient Operating Temperature -25 to +40°C (derating above 40°C: 95 A at 45°C, 90 A at 50°C, 85 A at 55°C, 80 A at 60°C)
Storage/Transport Temperature -35 to +60°C
Housing Colour Gray, RAL 7035
Standards IEC/EN 61008

V. Model Description

PFIM-100/2/01 code structure: PFIM denotes the xPole residual current device series (10 kA); 100 is the rated current 100 A; 2 denotes two-pole; 01 is the rated residual operating current 100 mA. Other codes in the series: 001 = 10 mA, 003 = 30 mA, 03 = 300 mA, 05 = 500 mA. Without an -A/-G suffix the device is Type AC; -A denotes Type A (AC and pulsating DC sensitive) and -G the short-time-delay Type G.

VI. Why Choose Us

  • Professional channel supply, comprehensive model coverage across multiple brands of low-voltage distribution and protective devices
  • Strict quality inspection process ensuring reliable product quality
  • Professional engineering team providing technical support and selection consultation
  • Quick response, efficient logistics, orders accepted
  • Quality assurance, worry-free after-sales service

VII. FAQ

Q1: What is the PFIM-100/2/01?

A: A 2-pole residual current circuit breaker of the xPole PFIM series, 100 A, 100 mA, Type AC, for fault current protection and additional personal protection.

Q2: What is the residual operating current of this model?

A: 100 mA with instantaneous non-delayed tripping; the 30 mA version in the same series is PFIM-100/2/003.

Q3: Can it be used in a 400 V three-phase circuit?

A: This model is 2-pole with a rated operational voltage of 230 V AC, intended for single-phase circuits; three-phase applications require a 4-pole model.

Q4: What are the installation and wiring requirements?

A: Quick mounting on 35 mm DIN rail with supply connectable to either side; single-core conductors 1.5 to 35 mm², terminal torque 2 to 2.4 N·m, and the T button should be pressed every 6 months for functional testing per IEC/EN 61008.