Eaton PFIM-100/2/01 Residual Current Circuit Breaker (100 A, 2P, 100 mA, Type AC)
I. Product Overview
The PFIM-100/2/01 is a 2-pole residual current circuit breaker (RCCB) of the xPole PFIM series, with a rated current of 100 A, a rated residual operating current of 100 mA, and Type AC sensitivity (AC sensitive, pulse-current sensitive), with instantaneous non-delayed tripping.
The device conforms to IEC/EN 61008, with a rated short-circuit strength of 10 kA, rated insulation voltage of 440 V and rated impulse withstand voltage of 4 kV. Tripping is line-voltage independent, making it suitable for fault current/residual current protection and additional protection; the supply may be connected to either side and the device functions irrespective of mounting position. The housing is gray (RAL 7035) with a red/green real contact position indicator, twin-purpose lift/open-mouthed terminals, and supports standard busbar connection as well as subsequent mounting of auxiliary and tripping signal switches.
II. Specifications
表格
| Parameter | Value |
|---|---|
| Model | PFIM-100/2/01 |
| Series | xPole PFIM |
| Product Type | Residual current circuit breaker (RCCB), Type AC |
| Poles | 2P |
| Rated Current In | 100 A |
| Rated Residual Operating Current IΔn | 100 mA |
| Sensitivity | AC sensitive (Type AC, pulse-current sensitive) |
| Tripping Characteristic | Instantaneous, non-delayed |
| Rated Operational Voltage Ue | 230 V AC (2-pole) |
| Rated Frequency | 50 Hz |
| Rated Insulation Voltage Ui | 440 V |
| Rated Impulse Withstand Voltage Uimp | 4 kV (1.2/50 μs) |
| Rated Short-circuit Strength | 10 kA |
| Rated Making and Breaking Capacity Im | 1000 A (In = 100 A) |
| Maximum Back-up Fuse | 100 A gG/gL |
| Electrical Endurance | ≥4000 switching operations |
| Mechanical Endurance | ≥20000 operations |
| Dimensions | 80 mm H × 76 mm D × 35 mm W (2 modules) |
| Mounting | 35 mm DIN rail (IEC/EN 60715), quick fastening with 2 lock-in positions |
| Terminals | Twin-purpose lift/open-mouthed, top and bottom; single wire 1.5 to 35 mm², multi-wire 2 × 16 mm²; torque 2 to 2.4 N·m, M5 screws |
| Test Button Voltage Range | 196 to 264 V AC (2-pole) |
| Degree of Protection | IP40 (built-in); IP54 in moisture-proof enclosure |
| Ambient Operating Temperature | -25 to +40°C (derating above 40°C: 95 A at 45°C, 90 A at 50°C, 85 A at 55°C, 80 A at 60°C) |
| Storage/Transport Temperature | -35 to +60°C |
| Housing Colour | Gray, RAL 7035 |
| Standards | IEC/EN 61008 |
V. Model Description
PFIM-100/2/01 code structure: PFIM denotes the xPole residual current device series (10 kA); 100 is the rated current 100 A; 2 denotes two-pole; 01 is the rated residual operating current 100 mA. Other codes in the series: 001 = 10 mA, 003 = 30 mA, 03 = 300 mA, 05 = 500 mA. Without an -A/-G suffix the device is Type AC; -A denotes Type A (AC and pulsating DC sensitive) and -G the short-time-delay Type G.
VI. Why Choose Us
- Professional channel supply, comprehensive model coverage across multiple brands of low-voltage distribution and protective devices
- Strict quality inspection process ensuring reliable product quality
- Professional engineering team providing technical support and selection consultation
- Quick response, efficient logistics, orders accepted
- Quality assurance, worry-free after-sales service
VII. FAQ
Q1: What is the PFIM-100/2/01?
A: A 2-pole residual current circuit breaker of the xPole PFIM series, 100 A, 100 mA, Type AC, for fault current protection and additional personal protection.
Q2: What is the residual operating current of this model?
A: 100 mA with instantaneous non-delayed tripping; the 30 mA version in the same series is PFIM-100/2/003.
Q3: Can it be used in a 400 V three-phase circuit?
A: This model is 2-pole with a rated operational voltage of 230 V AC, intended for single-phase circuits; three-phase applications require a 4-pole model.
Q4: What are the installation and wiring requirements?
A: Quick mounting on 35 mm DIN rail with supply connectable to either side; single-core conductors 1.5 to 35 mm², terminal torque 2 to 2.4 N·m, and the T button should be pressed every 6 months for functional testing per IEC/EN 61008.