Yokogawa UT32A-000-10-00 Digital Indicating Controller (48×96 mm Single-loop)

The UT32A-000-10-00 is a 48×96 mm panel-mount digital indicating controller from the UTAdvanced series with single-loop control, one universal input (thermocouple, RTD, DC voltage or DC current), a 5-digit 14-segment color LCD, a 200 ms control period, 2 DIs and 3 DOs as standard, one control output (4 to 20 mA or voltage pulse) plus one retransmission output shared with a 15 V DC loop power supply, 100 to 240 V AC supply and IP66 front panel, for single-loop PID control of temperature and proce
online consultation

Product Details

I. Product Overview

The UT32A-000-10-00 is a general-purpose digital indicating controller of the Yokogawa UTAdvanced series, panel mounted in a 48 × 96 mm portrait format with a 65 mm depth behind the panel, suited to compact instrument panels.

This model is the standard type (basic control) with single-loop control and one universal input that accepts thermocouples, 3-wire RTDs, DC voltage and DC current directly without changing input cards. The display uses a 5-digit 14-segment active color LCD (PV color changing) with a 13.0 mm PV character height, plus a 5-digit data display and a 12-segment bar graph. The control period is 200 ms and supports PID, ON/OFF, two-position two-level and heating/cooling control with four target setpoints and PID parameter groups, auto-tuning, the "Super" overshoot-suppressing function and the "Super 2" hunting-suppressing function.

As standard it provides 2 no-voltage/transistor contact inputs, 3 relay outputs (1c control output plus three 1a alarm outputs), one control output configurable as 4 to 20 mA current or voltage pulse, and one retransmission output shared with a 15 V DC loop power supply. A ladder sequence function (max. 300 steps) is built in. The front panel is IP66 (NEMA4, hose-down test only) and the operating ambient temperature is -10 to 50°C.

The third character of this model code is 0, so it does not include RS-485, Ethernet, CC-Link, PROFIBUS-DP or DeviceNet communication.

II. Specifications

表格

Parameter Value
Model UT32A-000-10-00
Product Type Digital indicating controller (panel mounting, standard type, single-loop)
Series UTAdvanced
External Dimensions 48 (W) × 96 (H) × 65 (depth behind panel) mm
Panel Cutout 45 +0.6 × 92 +0.8 mm
Weight 0.5 kg or less
Case Material Polycarbonate resin (flame retardancy UL94 V-0)
Case Color White (light gray)
Display PV: 5-digit 14-segment active color LCD (white/red), character height 13.0 mm; data: 5-digit 11-segment orange LCD; bar graph: 12 segments
Control Mode Single-loop control; PID, ON/OFF, two-position two-level, heating/cooling
Control Period 200 ms
Setpoint / PID Groups Four each (target setpoints, alarm setpoints, PID parameters)
Control Parameter Range Proportional band 0.1 to 999.9%; integral time 1 to 6000 s or OFF; derivative time 1 to 6000 s or OFF
Input Points 1 (universal input)
Input Types Thermocouple (K, J, E, T, B, R, S, N, U, W, Platinel II, Re3-W75, W97Re25, PR20-40), 3-wire RTD (Pt100, JPt100), DC voltage (0.4 to 2.000 V, 1 to 5.000 V, 0 to 2.000 V, 0 to 10.00 V, -10.00 to 20.00 mV), DC current (4.00 to 20.00 mA, 0.00 to 20.00 mA)
Input Accuracy ±0.1% of instrument range ±1 digit (standard operating conditions 23±2°C, 55±10%RH)
Input Sampling Period Synchronized to the control period
Contact Inputs 2 points (no-voltage contact or transistor contact, 12 V DC, 10 mA or more)
Control Output (heating side) 1 point: 4 to 20 mA DC or 0 to 20 mA DC (load ≤600 Ω), or voltage pulse (ON ≥12 V, OFF ≤0.1 V DC, load ≥600 Ω); time resolution 10 ms or 0.1% of output value, whichever is larger
Retransmission Output 1 point (shared with 15 V DC loop power supply): 4 to 20 mA DC or 0 to 20 mA DC, load ≤600 Ω; accuracy ±0.1% of span
15 V DC Loop Power Supply 1 point (shared with retransmission output): 14.5 to 18.0 V DC, max. approx. 21 mA (with short-circuit current limiting)
Relay Contact Outputs Control output 1c: 3 A at 250 V AC / 3 A at 30 V DC (resistive load); 3 alarm outputs 1a: 1 A at 240 V AC / 1 A at 30 V DC (resistive load, common separated)
Alarm Points Up to 8 (depending on model code)
Alarm Types PV high/low, deviation high/low, deviation within/outside band, analog input PV high/low, feedback input high/low, PV rate-of-change, SP high/low, target SP high/low and deviation, control output high/low, heater break (/HA option), self-diagnosis
Ladder Sequence 13 basic and 73 application commands, max. 300 steps; computation period same as control period
Communication Not included in this model (third character 0)
Power Supply 100 to 240 V AC (+10%/-15%), 50/60 Hz
Power Consumption 15 VA
Allowable Power Interruption 20 ms (at 100 V AC)
Insulation Resistance 20 MΩ or more at 500 V DC
Withstanding Voltage 2300 V AC for 1 minute between primary and secondary terminals (UL/CSA), 3000 V AC for 1 minute (CE)
Operating Ambient Temperature -10 to 50°C (side-by-side close mounting -10 to 40°C)
Operating Ambient Humidity 20 to 90% RH (no condensation)
Continuous Vibration 5 to 9 Hz half amplitude 1.5 mm or less; 9 to 150 Hz 4.9 m/s² or less
Shock 98 m/s² or less, 11 ms
Installation Altitude 2000 m or less above sea level
Degree of Protection IP66 (front panel), NEMA4 (hose-down test only); not applicable to side-by-side close mounting
Safety Standards IEC/EN 61010-1, IEC/EN 61010-2-201, IEC/EN 61010-2-030, UL 61010-1, CAN/CSA C22.2 No.61010-1
EMC Standards EN 61326-1 Class A, EN 61326-2-3, EN 55011 Class A Group 1
Terminals M3 screw terminal with square washer

V. Model Description

UT32A-000-10-00 resolved against the official model and suffix code table: UT32A is the panel-mounting digital indicating controller (100 to 240 V AC supply, provided with retransmission output or 15 V DC loop power supply, 2 DIs and 3 DOs); the first 0 is the basic control standard type (-1 position proportional, -2 heating/cooling); the second 0 is no additional DI/DO (standard configuration is 2 DIs and 3 DOs); the third 0 is no open network communication (1 would be RS-485); the fourth 1 is English display language (switchable); the fifth 0 is the white (light gray) case; the final -00 is a fixed code.

VI. Why Choose Us

  • Professional channel supply, comprehensive model coverage across multiple brands of process instrumentation and control system spare parts
  • Strict quality inspection process ensuring reliable product quality
  • Professional engineering team providing technical support and selection consultation
  • Quick response, efficient logistics, orders accepted
  • Quality assurance, worry-free after-sales service

VII. FAQ

Q1: Which input signals does the UT32A-000-10-00 accept? A: One universal input supporting thermocouples, 3-wire RTDs, DC voltage and DC current; see the specifications for the full input type list.

Q2: Does this model include communication? A: No. The third code character is 0, meaning no RS-485, Ethernet, CC-Link, PROFIBUS-DP or DeviceNet.

Q3: What form is the control output? A: One output, configurable as 4 to 20 mA (or 0 to 20 mA) current output or as voltage pulse output for driving solid state relays.

Q4: How to confirm panel cutout and power supply? A: Cutout 45 +0.6 × 92 +0.8 mm, body 48 × 96 × 65 mm; supply 100 to 240 V AC at 15 VA; operating ambient -10 to 50°C with IP66 front panel.