Mitsubishi FX5-16EX/ES MELSEC iQ-F 16-Point Digital Input Extension Module

The FX5-16EX/ES is a 16-point digital input extension module for the MELSEC iQ-F series, with 24 V DC input (+20%/-15%), sink/source selectable input, M3 screw terminal block wiring, 5.6 kΩ input impedance and 4.0 mA input current, ON sensitivity of 3.0 mA or more and OFF of 1.5 mA or less, response time of 50 μs or less ON and 150 μs or less OFF, photocoupler isolation and per-point LED indication, for I/O expansion of FX5U, FX5UC, FX5UJ and MX-F controllers.
online consultation

Product Details

I. Product Overview

The FX5-16EX/ES is a digital input extension module of the Mitsubishi Electric MELSEC iQ-F series, adding 16 DC input points to FX5U, FX5UC and FX5UJ CPU modules and to MX Controller MX-F models. It uses a screw terminal block with M3 screws, giving straightforward wiring and easy field maintenance.

The module accepts sink/source input types and can be powered from the CPU's 24 V DC service power supply or from an external 24 V supply, with the internal 5 V supplied by the PLC. The input circuit is photocoupler isolated and accepts no-voltage contacts as well as NPN (sink) or PNP (source) open collector transistor sensors, with an LED lit for each input that is ON.

Input characteristics: signal voltage 24 V DC +20%/-15%, input current 4.0 mA at 24 V DC, input impedance 5.6 kΩ, ON sensitivity current 3.0 mA or more and OFF 1.5 mA or less; response time 50 μs or less for ON and 150 μs or less for OFF, suitable for general switch and sensor signal acquisition. The module weighs approximately 0.25 kg and its general specifications are the same as those of the CPU module used. An FX5-CNV-IFC or FX5-C1PS-5V converter is required when connecting to an FX5UC CPU module or an MX-F model.

II. Specifications

表格

Parameter Value
Model FX5-16EX/ES
Product Type Digital input extension module (16 points, screw terminal block type)
Applicable CPU Modules FX5U, FX5UC, FX5UJ; MX Controller MX-F models
Connection Converter FX5-CNV-IFC or FX5-C1PS-5V required for FX5UC or MX-F
Number of Input Points 16
Input Connection Type Screw terminal block (M3 screws)
Input Type Sink/source
Input Signal Voltage 24 V DC +20%/-15%
Input Signal Current 4.0 mA at 24 V DC
Input Impedance 5.6 kΩ
Input Sensitivity Current (ON) 3.0 mA or more
Input Sensitivity Current (OFF) 1.5 mA or less
Input Response Time ON: 50 μs or less; OFF: 150 μs or less
Input Signal Format No-voltage contact input; sink: NPN open collector transistor; source: PNP open collector transistor
Input Circuit Insulation Photocoupler isolation
Input Operation Indication LED lit when input is ON
Rated Voltage 24 V DC (from 24 V DC service power supply or external supply); 5 V DC (supplied internally from the PLC)
Current Consumption (5 V DC) 100 mA
Current Consumption (24 V DC) 85 mA
Mass Approx. 0.25 kg
General Specifications Same as the CPU module used
Conformity UL, cUL, CE (EMC), CE (RoHS), KC (EMC); classification societies LR, NK, DNV, ABS, RINA, BV, KR

V. Model Description

FX5-16EX/ES belongs to the MELSEC iQ-F extension module family: FX5 is the series designation, 16 is the point count, EX denotes the input (extension input) unit and ES corresponds to the sink/source input type stated officially. Other models in the family include FX5-8EX/ES (8 inputs), FX5-16ER/ES (16 relay outputs), FX5-16ET/ES and FX5-16ET/ESS (16 transistor outputs), allowing selection by point count and output type.

VI. Why Choose Us

  • Professional channel supply, comprehensive model coverage across Mitsubishi PLC and factory automation spare parts
  • Strict quality inspection process ensuring reliable product quality
  • Professional engineering team providing technical support and selection consultation
  • Quick response, efficient logistics, orders accepted
  • Quality assurance, worry-free after-sales service

VII. FAQ

Q1: How many input points does this module provide?

A: 16 points, 24 V DC, sink/source selectable.

Q2: Which CPU modules can it be used with?

A: FX5U, FX5UC and FX5UJ as well as MX Controller MX-F; FX5-CNV-IFC or FX5-C1PS-5V is required for FX5UC or MX-F.

Q3: What is the input response time?

A: 50 μs or less for ON and 150 μs or less for OFF.

Q4: How is wiring and indication arranged?

A: M3 screw terminal block wiring, photocoupler-isolated inputs, with an LED lit for each input that is ON.