ꄶ Fluid Power
-
ꄶ Test & Measurement
-
ꄶ Analytical Inst.
-
ꄶ Power Transmission
-
ꄶ Electrical
-
ꄶ Automation
-
ꁇ VFDs
-
ꁇ Modules
-
ꁇ Control Systems
-
ꁇ Sensors
-
Proximity Sensors
-
Temperature Sensors
-
Photoelectric Sensors
-
Pressure Sensors
-
Magnetostrictive Sensors
-
Ultrasonic Sensors
-
Load Cells
-
Linear Displacement Sensors
-
Torque Sensors
-
Displacement Sensors
-
Inductive Sensors
-
Vibration Sensors
-
Pulse Sensors
-
Other Sensors
-
Angle Sensors
-
Temperature Digital Indicators
-
Turbidity Sensors
-
Probes
-
-
ꁇ Industrial Computers
-
ꁇ Encoders
-
ꁇ Servo Systems
-
-
ꄶ Thermal
Danfoss FC-302N250T5E20H2XGCXXXSXXXXAQBKCXXXXDX Variable Frequency Drive (250 kW / 380-500 V / Modbus TCP)
I. Product Overview
This product is a drive of the Danfoss VLT AutomationDrive FC 302 range (FC 301 is the standard version, FC 302 the advanced high-dynamic version), used for variable speed control of three-phase induction motors and permanent magnet motors. This variant is rated 250 kW at 400 V, 350 hp at 460 V and 315 kW at 500 V, with the normal overload specification (110% current for 60 s) and a three-phase 380-500 VAC mains supply.
Output capability: at 400 V the continuous output current is 480 A, the 60-second intermittent overload current 528 A and the continuous apparent power 333 kVA; at 460 V the continuous output current is 443 A with 353 kVA continuous apparent power; at 500 V the continuous output current is 443 A. The chassis is D4h with IP20 protection (chassis mounting).
Configuration: this variant uses an H2 RFI filter (A2 class / C3 class), has no brake chopper, is fitted with the graphical local control panel LCP-102, has a coated PCB (for humid and corrosive-gas environments), has no mains options (no breaker, fuses, contactor or load-sharing terminals), standard cable entry, no heatsink air-flow duct, standard software and standard language pack.
Built-in options: A option is the Modbus TCP fieldbus card MCA 122; B option is the general purpose I/O card MCB 101 (adding digital and analog I/O); the C option and C1 option positions are empty (no MCO 305 motion control card, no MCB 113 extended relay card) with the standard controller; the D option position is empty (no MCB 107 24 V DC backup supply). Safe Torque Off (STO) with a dedicated safety input (terminal 37) is part of the standard drive configuration.
The range is intended for applications with high demands on dynamics, control accuracy and process integration, supporting a single-drive concept from ordinary variable speed duty to servo-like operation on any machine or production line, and can be extended with a wide range of fieldbus and functional options.
II. Specifications
表格
| Parameter | Value |
|---|---|
| Type Code | FC-302N250T5E20H2XGCXXXSXXXXAQBKCXXXXDX |
| Product Range | VLT AutomationDrive FC 302 (advanced) |
| Rated Power (400 V) | 250 kW |
| Rated Power (460 V) | 350 hp |
| Rated Power (500 V) | 315 kW |
| Overload | Normal overload 110% for 60 s |
| Mains Supply | 3-phase 380-500 VAC |
| Output Current (400 V, continuous) | 480 A |
| Output Current (400 V, 60 s overload) | 528 A |
| Output Current (460/500 V, continuous) | 443 A |
| Continuous Apparent Power (400 V) | 333 kVA |
| Continuous Apparent Power (460 V) | 353 kVA |
| Chassis | D4h |
| Degree of Protection | IP20 (chassis) |
| Dimensions (H × W × D) | 1027 × 375 × 375 mm |
| Weight | 125 kg |
| RFI Filter | H2: A2 class (C3 class) |
| Brake Chopper | None (X) |
| Local Control Panel | Graphical LCP (LCP-102) |
| PCB Coating | Coated (C) |
| Mains Options | None (X) |
| Fieldbus (A option) | Modbus TCP, MCA 122 (AQ) |
| Extension I/O (B option) | General Purpose I/O MCB 101 (BK) |
| C Option / C1 Option | None (CX / X) |
| Controller Software | Standard controller (XX) |
| D Option | None (DX) |
| Safety Function | Safe Torque Off (STO) standard, terminal 37 |
V. Model Description
The 39-character type code reads as follows: FC-302 is the product group (VLT AutomationDrive FC 302); N250 is the 250 kW rating with N denoting normal overload; T is three-phase; 5 is the 380-500 VAC mains voltage; E20 is the IP20/chassis enclosure; H2 is the A2 class (C3) RFI filter; position 18 X means no brake chopper; G is the graphical LCP (LCP-102); C is coated PCB; position 21 X means no mains option; position 22 X is standard cable entry; position 23 X means no hardware adaptation; SXXX is the standard software version; X is the standard language pack; AQ is the A option Modbus TCP (MCA 122); BK is the B option general purpose I/O card (MCB 101); CX means no C option; position 35 X means no C1 option (MCB 113 extended relay card); XX is the standard controller; DX means no D option (MCB 107 24 V DC backup supply).
The range covers roughly 0.25 kW up to 710 kW and above with A, B, C, D and E frame sizes; selection starts from the motor current and overload requirement (110% normal or 150% high overload) to determine the power code, then the A/B/C/D options are chosen according to fieldbus, I/O, safety and braking needs.
VI. Why Choose Us
- Professional channel supply covering Danfoss VLT drives and matching options
- Strict quality inspection process ensuring reliable product quality
- Professional engineering team providing technical support and selection consultation
- Quick response, efficient logistics, orders accepted
- Quality assurance, worry-free after-sales service
VII. FAQ
Q1: What are the power and voltage ratings of this model?
A: 250 kW at 400 V / 350 hp at 460 V / 315 kW at 500 V, with a three-phase 380-500 VAC supply and 110% normal overload for 60 s.
Q2: Which communication interface is included?
A: The Modbus TCP fieldbus card MCA 122 (A option) and the general purpose I/O card MCB 101 (B option).
Q3: What are the protection class and dimensions?
A: D4h chassis, IP20, 1027 × 375 × 375 mm, weight 125 kg.
Q4: Does it have a brake chopper?
A: This variant has no brake chopper (code X); a variant with the built-in brake chopper requires the letter B in position 18.