Vaisala DMT143 Miniature Dew Point Transmitter (-70…+60 °C Td / Modbus RTU / IP66)
I. Product Overview
This product is a Vaisala DRYCAP miniature dew point transmitter designed for dew point measurement in small compressed air dryers, plastic dryers, additive production and other OEM applications. It can be installed directly into pressurised systems at a maximum measurement pressure of 50 bar(a) (725 psia), and its small size and low weight make it quick to install in tight spaces or small-diameter pipelines; it can also be used with the Vaisala DM70 handheld dew point meter.
For measurement technology, it uses the DRYCAP 180D sensor with Vaisala's unique autocalibration function, which detects possible measurement inaccuracies and automatically corrects dry-end drift of the calibration curve, ensuring long-term accuracy and extending the calibration interval to 2 years. The sensor fully withstands getting wet, so the transmitter performs well in applications that occasionally see process water spikes, such as pipeline condensation during a system failure or start-up; it is also highly resistant to particulate contamination, oil vapour and most chemicals, and is insensitive to flow rate. Sensor protection is a stainless steel sintered filter.
Measurement performance: the typical dew point range is -70 to +60 °C Td (-94 to +140 °F) with ±2 °C Td accuracy in air or nitrogen (±4 °C Td above 12 bar); below 0 °C the transmitter outputs frost point. Water concentration by volume range is 10 to 40,000 ppm with accuracy of 1 ppm + 20% of reading at +20 °C and 1 bar. Response time (63%/90%) is typically 5 s/15 s from -70 to -20 °C Td and 45 s/10 min from -20 to -70 °C Td. Analog output scaling options are -80 to +20 °C Td, -80 to +20 °C Td dew point at ambient pressure, or free scaling.
Outputs and supply: analog output supports 4 to 20 mA (3-wire), 0 to 1 V / 5 V and 1 to 5 V; the digital output is RS-485 (non-isolated) supporting the Vaisala industrial protocol and Modbus RTU. Operating voltage is 12 to 28 VDC with digital or voltage output and 18 to 28 VDC with current output; load is 500 Ω maximum for current output and 10 kΩ minimum for voltage output. The connector is a 4-pin M8 (IEC 60947-5-2). At +20 °C and 24 VDC the supply current is typically 10 mA plus load current in normal measurement and 220 mA pulsed during self-diagnostics. For temperatures below 0 °C or pressures above 20 bar(a), the supply voltage must be 24 to 28 VDC.
Environment and construction: measurement media are air, nitrogen, hydrogen, argon, helium and oxygen; operating temperature -40 to +60 °C, relative humidity 0 to 100% RH, storage temperature -40 to +60 °C; protection class IP66. Mechanical connections are available as ISO 228-1 G1/2", 1/2" NPT, 3/4"-16 UNF or 5/8"-18 UNF; the housing is AISI 316L stainless steel; weight is 90 g for G and UNF thread versions and 100 g for the NPT version; overall length is 91.6 mm, body diameter Ø28 mm and probe diameter Ø12 mm.
The product complies with the EMC Directive 2014/30/EU and RoHS Directive 2011/65/EU as amended by 2015/863, with EMC performance to IEC/EN 61326-1 industrial environment and CISPR 32 / EN 55032 Class B, and carries CE, China RoHS, RCM and UKCA marks.
II. Specifications
表格
| Parameter | Value |
|---|---|
| Model | DMT143 |
| Product Type | Miniature dew point transmitter |
| Sensor | DRYCAP 180D |
| Sensor Protection | Stainless steel sintered filter |
| Recommended Calibration Interval | 2 years |
| Dew Point Range (typical) | -70 to +60 °C Td (-94 to +140 °F) |
| Accuracy (air or N2) | ±2 °C Td; ±4 °C Td above 12 bar |
| Analog Output Scaling | Option 1: -80 to +20 °C Td; Option 2: -80 to +20 °C Td at ambient pressure; Option 3: free scaling |
| Response Time 63%/90% (-70→-20 °C Td) | Typically 5 s / 15 s |
| Response Time 63%/90% (-20→-70 °C Td) | Typically 45 s / 10 min |
| Water Concentration Range | 10 to 40,000 ppm |
| Water Concentration Accuracy (+20 °C, 1 bar) | 1 ppm + 20% of reading |
| Measurement Media | Air, nitrogen, hydrogen, argon, helium, oxygen |
| Operating Temperature | -40 to +60 °C |
| Relative Humidity | 0 to 100% RH |
| Measurement Pressure | 0 to 50 bar(a) (725 psia) |
| Storage Temperature | -40 to +60 °C |
| Degree of Protection | IP66 |
| Analog Output | 4 to 20 mA (3-wire), 0 to 1 V / 5 V, 1 to 5 V |
| Current Output Resolution / Accuracy | 0.002 mA / ±0.05 mA at +20 °C |
| Voltage Output Resolution / Accuracy | 0.3 mV / ±0.01 V at +20 °C |
| Digital Output | RS-485 (non-isolated) |
| Protocols | Vaisala industrial protocol, Modbus RTU |
| Operating Voltage | 12 to 28 VDC (digital/voltage output); 18 to 28 VDC (current output) |
| Output Load | 500 Ω max. (current); 10 kΩ min. (voltage) |
| Temperature Dependence | 0.005% of span/°C |
| Connector | 4-pin M8 (IEC 60947-5-2) |
| Mechanical Connection | ISO 228-1 G1/2", 1/2" NPT, 3/4"-16 UNF, 5/8"-18 UNF |
| Housing Material | Stainless steel AISI 316L |
| Weight | 90 g (G/UNF thread); 100 g (NPT thread) |
| Dimensions | Overall length 91.6 mm; body Ø28 mm; probe Ø12 mm |
| Compliance | EMC 2014/30/EU, RoHS 2011/65/EU; IEC/EN 61326-1, CISPR 32/EN 55032 Class B; CE, China RoHS, RCM, UKCA |
V. Model Description
DMT143 is the miniature (short) dew point transmitter; the same series also includes DMT143L (long version), and the long version has replaced DMT242. A complete order code combines the mechanical connection thread (G1/2", 1/2" NPT, 3/4"-16 UNF, 5/8"-18 UNF), digital and analog output type, analog scaling option, sensor configuration and pressure setting, so several suffix configurations exist under the DMT143 name and selection should be checked against the specific order code.
Accessories include the USB cable for PC connection (219690), DM70 connection cable M12-M8 (219980SP), loop-powered external display (226476, and 234759 with relays) and a range of sampling cells (DMT242SC, DMT242SC2, DSC74SP, DSC74BSP, DMCOILSP and others) to suit different sampling arrangements.
VI. Why Choose Us
- Professional channel supply covering Vaisala dew point instruments and sampling accessories
- Strict quality inspection process ensuring reliable product quality
- Professional engineering team providing technical support and selection consultation
- Quick response, efficient logistics, orders accepted
- Quality assurance, worry-free after-sales service
VII. FAQ
Q1: What are the measurement range and accuracy?
A: Typically -70 to +60 °C Td, with ±2 °C Td in air or nitrogen and ±4 °C Td above 12 bar.
Q2: Which outputs are available?
A: Analog 4 to 20 mA (3-wire) or 0 to 1 V / 5 V and 1 to 5 V, plus RS-485 digital output supporting Modbus RTU.
Q3: Can it be installed directly in a pressurised pipeline?
A: Yes, up to 50 bar(a) measurement pressure, with an operating temperature of -40 to +60 °C.
Q4: What are the protection class and materials?
A: IP66, AISI 316L stainless steel housing, 90 g for G/UNF thread versions and 100 g for the NPT version.