ABB AF400-30-11 3-Pole Block Contactor (100-250 V AC/DC Coil / AC-3 400 A / 200 kW at 400 V)
I. Product Overview
The AF400-30-11 is a 3-pole block contactor built on AF technology, with three normally open main contacts (no normally closed main poles) and 1 NO + 1 NC auxiliary contacts pre-mounted on the body. Its key feature is the electronically controlled coil: a single coil covers 100 to 250 V at 50 Hz, 60 Hz and DC, so the contactor operates reliably in networks with large control voltage variations, with surge protection built in and no additional overvoltage components required.
To IEC 60947-4-1, in AC-3 utilization category at 55°C the rated operational current is 400 A (400 A at 220/230/240 V, 380/400 V, 415 V, 440 V and 500 V; 350 A at 690 V; 155 A at 1000 V), corresponding to AC-3 motor ratings of 110 kW at 220 to 240 V, 200 kW at 380/400 V, 220 kW at 415/440 V, 250 kW at 500 V and 315 kW at 690 V. In AC-1 the conventional free-air thermal current is 600 A at 40°C, 500 A at 55°C and 400 A at 70°C; for DC-1, DC-3 and DC-5 the rating is 600 A at 110 V single-pole, 220 V with three poles in series and 600 V with three poles in series.
Short-circuit protection is gG fuses of 630 A; rated short-time withstand current Icw is 4600 A for 10 s and 1 min, 2500 A for 30 s and 3100 A for 15 min, with maximum breaking capacity of 4000 A at 440 V and 3500 A at 690 V. Rated insulation voltage is 1000 V and rated impulse withstand voltage 8 kV. Mechanical durability is 3 million operations, with maximum switching frequency of 300 cycles per hour in AC-1 and AC-3 and 60 cycles per hour in AC-2/AC-4. Power loss is 32 W per pole in AC-1 and 14 W per pole in AC-3.
Coil data: pull-in 1155 V·A; holding 32.6 V·A (4.8 W) at 50/60 Hz and 4.5 W at DC; operating limits 0.85 to 1.1 × Uc at ambient ≤70°C. Operate times are 45 to 55 ms from de-energization to NC closing, 48 to 58 ms from de-energization to NO opening, 45 to 115 ms from energization to NC opening and 50 to 120 ms from energization to NO closing.
Construction and connection: main circuit bar terminals accept 2×240 mm² copper or aluminium cable, with M10 main pole screws at 35 N·m tightening torque; auxiliary circuits accept 2×0.75 to 2.5 mm² flexible conductors or 2×1 to 4 mm² solid/stranded conductors. Coil terminals are IP20 and main terminals IP00. Dimensions are 186 × 216 × 278 mm and net weight 10.6 kg.
Environmental capability: operating and storage temperature -40 to 70°C (-25 to 50°C with a thermal overload relay mounted alongside), no derating up to 3000 m altitude and 5 g shock resistance to IEC 60068-2-27. The product carries CE, UKCA, cULus and CB approvals plus ABS, BV, CCS, LR, PRS and RINA classification certificates, with customs tariff number 85364900.
II. Specifications
表格
| Parameter | Value |
|---|---|
| Model | AF400-30-11 |
| Product ID | 1SFL577001R9100 |
| EAN | 7320500220153 |
| Product Type | 3-pole block contactor (AF electronic coil) |
| Main Contacts | 3 NO |
| Auxiliary Contacts | 1 NO + 1 NC |
| Number of Poles | 3P |
| Rated Operational Voltage (main circuit) | 1000 V (IEC); 600 V (UL) |
| Rated Frequency | 50/60 Hz |
| Conventional Free-air Thermal Current Ith | 600 A (40°C, open contactors, IEC 60947-4-1) |
| Rated Operational Current AC-1 | 600 A (40°C) / 500 A (55°C) / 400 A (70°C) at 690 V and 1000 V |
| Rated Operational Current AC-3 | 400 A (220 to 240 V, 380/400 V, 415 V, 440 V, 500 V at 55°C); 350 A (690 V); 155 A (1000 V) |
| Rated Operational Current DC-1/DC-3/DC-5 | 600 A (110 V single pole; 220 V three poles in series; 600 V three poles in series, 40°C) |
| Rated Operational Power AC-3 | 110 kW (220 to 240 V); 200 kW (380/400 V); 220 kW (415/440 V); 250 kW (500 V); 315 kW (690 V) |
| Making Capacity AC-3 | 10 × Ie |
| Breaking Capacity AC-3 | 8 × Ie |
| Short-Circuit Protection | gG fuses 630 A |
| Short-time Withstand Current Icw | 4600 A for 10 s / 1 min; 2500 A for 30 s; 3100 A for 15 min (40°C) |
| Maximum Breaking Capacity | 4000 A at 440 V; 3500 A at 690 V |
| Rated Insulation Voltage Ui | 1000 V |
| Rated Impulse Withstand Voltage Uimp | 8 kV (main circuit) |
| Mechanical Durability | 3 million operations |
| Maximum Switching Frequency | AC-1 300 cycles/h; AC-2/AC-4 60 cycles/h; AC-3 300 cycles/h |
| Power Loss per Pole | 32 W in AC-1; 14 W in AC-3 |
| Rated Control Circuit Voltage Uc | 100 to 250 V (50 Hz, 60 Hz, DC) |
| Coil Operating Limits | 0.85 to 1.1 × Uc (≤70°C) |
| Pull-in Consumption | 1155 V·A |
| Holding Consumption | 32.6 V·A (4.8 W) at 50/60 Hz; 4.5 W at DC |
| Operate Time (de-energization) | 45 to 55 ms to NC closing; 48 to 58 ms to NO opening |
| Operate Time (energization) | 45 to 115 ms to NC opening; 50 to 120 ms to NO closing |
| Main Circuit Connection | Bar terminals; 2×240 mm² Cu/Al cable; 47 mm² bar |
| Auxiliary Circuit Connection | 2×0.75 to 2.5 mm² flexible; 2×1 to 4 mm² solid/stranded |
| Terminal Screw / Torque | Main poles M10, 35 N·m; control circuit M3.5 / Pozidriv 2 |
| Degree of Protection | Coil terminals IP20; main terminals IP00 |
| Dimensions | 186 × 216 × 278 mm |
| Net Weight | 10.6 kg |
| Operating / Storage Temperature | -40 to 70°C (-25 to 50°C with thermal overload relay alongside) |
| Installation Altitude | No derating up to 3000 m |
| Shock Resistance | 5 g (IEC 60068-2-27) |
| Approvals | CE, UKCA, cULus, CB, ABS, BV, CCS, CQC, LR, PRS, RINA |
| UL/CSA General Use Rating | 550 A at 600 V and 1000 V AC |
| UL/CSA Horsepower Rating | 125 hp (200 to 208 V); 150 hp (220 to 240 V); 350 hp (440 to 480 V); 400 hp (550 to 600 V) |
| UL Full Load Amps | 358.8 A (200 to 208 V); 360 A (220 to 240 V); 414 A (440 to 480 V); 382 A (550 to 600 V) |
| Customs Tariff Number | 85364900 |
V. Model Description
Per the ABB AF series naming convention: AF denotes a block contactor using AF technology (electronically controlled coil, wide control voltage range, built-in surge protection); 400 is the rating class (400 A AC-3, 200 kW at 400 V); 30 denotes 3 normally open main poles and 0 normally closed main poles; 11 denotes the pre-mounted auxiliary contacts of 1 NO + 1 NC. The official Product ID is 1SFL577001R9100, the 100-250 V AC/DC coil version; other variants in the family include AF400-30-00 (without auxiliary contacts) and AF400-30-11-70 with a different coil voltage suffix, so the suffix should be checked against the actual control voltage when ordering.
VI. Why Choose Us
- Professional channel supply, comprehensive model coverage across ABB low-voltage apparatus and industrial automation spare parts
- Strict quality inspection process ensuring reliable product quality
- Professional engineering team providing technical support and selection consultation
- Quick response, efficient logistics, orders accepted
- Quality assurance, worry-free after-sales service
Q1: What motor size can this contactor drive?
A: In AC-3 it controls a 200 kW motor at 380/400 V (400 A at 55°C), 220 kW at 415/440 V, 250 kW at 500 V and 315 kW at 690 V.
Q2: What is the coil voltage?
A: 100 to 250 V universal, at 50 Hz, 60 Hz or DC, with operating limits of 0.85 to 1.1 × Uc and built-in surge protection.
Q3: How many auxiliary contacts does it have?
A: 1 NO + 1 NC pre-mounted, with 3 NO main poles.
Q4: What short-circuit protection is required?
A: gG fuses of 630 A; Icw is 4600 A for 10 s.