ABB M1M 15 Modbus Multifunction Power Meter (96×96 Panel Mount / Modbus RTU / Class 1)
I. Product Overview
The M1M 15 Modbus is a multifunction power meter in the M1M range, intended for basic electrical parameter measurement and energy sub-metering on distribution circuits. It is a 96×96 mm panel-mount unit with a front LED display presenting three-phase readings on separate lines, side navigation LEDs and a four-button front keypad, using the same menu structure as the other M1M models.
Measurement inputs: the voltage channel accepts 80 to 265 VAC (line-to-neutral) and supports single-phase, three-phase three-wire (3P) and three-phase four-wire (3P+N) connections at a rated frequency of 50/60 Hz, with a T1 A-277 VAC protection fuse on the voltage circuit; the current channel is indirect via current transformers with a 1 A or 5 A secondary rating and no accuracy derating from 50 mA to 6 A. Sampling is 128 points per cycle, covering true RMS voltage and current, frequency, active/reactive/apparent power, power factor, timers and active/reactive/apparent energy, plus THD (current, phase voltage, line voltage) and unbalance as power quality parameters.
Accuracy follows IEC 61557-12 with an overall PMD/S/K55/1 rating: active energy Class 1, reactive energy Class 2, apparent power Class 1, active power Class 1, voltage Class 0.5, current Class 0.5, frequency Class 0.1, unbalance Class 0.5 and harmonics THD Class 5.
Communication is Modbus RTU over an optically isolated RS485 interface on a 3-pole terminal, with selectable baud rates of 9.6, 19.2, 38.4, 57.6 and 115.2 kbps, parity of Odd (1 stop bit), Even (1 stop bit) or None (1 or 2 stop bits), and slave addresses 1 to 247. This model has no digital inputs or outputs.
The auxiliary supply is 100 to 230 V AC/DC ±15% at 50 to 60 Hz with 5 VA maximum consumption, and the installation category is CAT III 300 V to IEC 61010-1 edition 3. Dimensions are 96×96 mm with 77 mm net depth and 0.315 kg net weight; front protection is IP51 and terminals IP20; operating temperature is -5 to 55°C and storage -25 to 70°C. Mounting uses tool-free clips with vertically arranged terminals for easy panel wiring.
II. Specifications
表格
| Parameter | Value |
|---|---|
| Model | M1M 15 Modbus |
| Order Code | 2TAZ661012R2000 |
| EAN | 6941593406999 |
| Product Type | Multifunction power meter (panel mount) |
| Display | LED |
| Dimensions | 96 × 96 × 77 mm |
| Net Weight | 0.315 kg |
| Mounting | Panel mount (tool-free clips) |
| Auxiliary Supply | 100 to 230 V AC/DC ±15% |
| Supply Frequency | 50 to 60 Hz |
| Maximum Consumption | 5 VA |
| Installation Category | CAT III 300 V (IEC 61010-1 edition 3) |
| Supply Protection Fuse | T1 A-277 VAC |
| Voltage Measurement Range | 80 to 265 VAC (L-N) |
| Connection Types | Single-phase, 3P, 3P+N |
| Rated Frequency | 50/60 Hz |
| Voltage Circuit Protection Fuse | T1 A-277 VAC |
| Current Input Mode | Indirect via current transformers (CT) |
| CT Secondary Rated Current | 1 A or 5 A |
| Range without Accuracy Derating | 50 mA to 6 A |
| Sampling | 128 points per cycle |
| Measured Parameters | TRMS voltage, TRMS current, frequency, active/reactive/apparent power, power factor, timers, active/reactive/apparent energy, THD (I, VLN, VLL), unbalance |
| Overall Standard | IEC 61557-12 PMD/S/K55/1 |
| Active Energy Accuracy | IEC 61557-12 Class 1 |
| Reactive Energy Accuracy | IEC 61557-12 Class 2 |
| Apparent Power Accuracy | IEC 61557-12 Class 1 |
| Active Power Accuracy | IEC 61557-12 Class 1 |
| Voltage Accuracy | IEC 61557-12 Class 0.5 |
| Current Accuracy | IEC 61557-12 Class 0.5 |
| Frequency Accuracy | IEC 61557-12 Class 0.1 |
| Unbalance Accuracy | IEC 61557-12 Class 0.5 |
| Harmonics THD Accuracy | IEC 61557-12 Class 5 |
| Communication Protocol | Modbus RTU |
| Communication Interface | RS485, optically isolated, 3-pole terminal |
| Baud Rate | 9.6 / 19.2 / 38.4 / 57.6 / 115.2 kbps |
| Parity | Odd (1 stop bit), Even (1 stop bit), None (1 or 2 stop bits) |
| Slave Address | 1 to 247 |
| Digital I/O | None |
| Degree of Protection | Front IP51; terminals IP20 (IEC 60529) |
| Operating Temperature | -5 to 55°C (K55, IEC 61557-12) |
| Storage Temperature | -25 to 70°C (K55, IEC 61557-12) |
| EMC | IEC 61326-1 |
| Electrical Safety | IEC 61010-1 |
V. Model Description
The M1M 15 Modbus belongs to the M1M family of panel-mount power meters: M1M is the series, 15 is the functional level (basic electrical parameters and energy metering with an LED display and no digital I/O), and Modbus denotes the built-in Modbus RTU communication over RS485. In the same family, the non-communicating M1M 15 has order code 2TAZ661010R2000; the M1M 20 Modbus adds THD and four-quadrant (import/export) measurement, the M1M 20 Ethernet provides Modbus TCP/IP, and the M1M 30 additionally supports harmonics to the 40th order with flash-memory data logging. Select the order code according to functional level and communication type.
VI. Why Choose Us
- Professional channel supply, comprehensive model coverage across ABB electrical measurement and distribution automation products
- Strict quality inspection process ensuring reliable product quality
- Professional engineering team providing technical support and selection consultation
- Quick response, efficient logistics, orders accepted
- Quality assurance, worry-free after-sales service
VII. FAQ
Q1: Which parameters can this meter measure?
A: True RMS voltage and current, frequency, active/reactive/apparent power, power factor, timers, and active/reactive/apparent energy plus THD and unbalance.
Q2: How are the current inputs connected?
A: Indirectly through current transformers with a 1 A or 5 A secondary rating, with no accuracy derating from 50 mA to 6 A.
Q3: How does communication work?
A: Optically isolated RS485 Modbus RTU, 9.6 to 115.2 kbps, addresses 1 to 247, on a 3-pole terminal.
Q4: What is the accuracy class?
A: IEC 61557-12 PMD/S/K55/1, with active energy Class 1, voltage and current Class 0.5 and frequency Class 0.1.