Products

넳 넲

Classification

Company Culture  ꄲ  Electrical  ꄲ  Electrical Meters  ꄲ  ABB AF400-30-11 3-Pole Block Contactor (100-250 V AC/DC Coil / AC-3 400 A / 200 kW at 400 V)
ꁆ ꁇ

ABB AF400-30-11 3-Pole Block Contactor (100-250 V AC/DC Coil / AC-3 400 A / 200 kW at 400 V)

The AF400-30-11 is a 3-pole block contactor using AF technology, with 3 NO main contacts and 1 NO + 1 NC pre-mounted auxiliary contacts, a wide 100-250 V coil (50/60 Hz and DC), built-in surge protection, AC-3 rating of 400 A at 55°C (controlling a 200 kW motor at 380-400 V), AC-1 capability up to 600 A at 40°C, 1000 V rated operational voltage, Icw of 4600 A for 10 s and 3 million operations mechanical durability, for motor control and power circuit switching.
online consultation

Product Details

I. Product Overview

The AF400-30-11 is a 3-pole block contactor built on AF technology, with three normally open main contacts (no normally closed main poles) and 1 NO + 1 NC auxiliary contacts pre-mounted on the body. Its key feature is the electronically controlled coil: a single coil covers 100 to 250 V at 50 Hz, 60 Hz and DC, so the contactor operates reliably in networks with large control voltage variations, with surge protection built in and no additional overvoltage components required.

To IEC 60947-4-1, in AC-3 utilization category at 55°C the rated operational current is 400 A (400 A at 220/230/240 V, 380/400 V, 415 V, 440 V and 500 V; 350 A at 690 V; 155 A at 1000 V), corresponding to AC-3 motor ratings of 110 kW at 220 to 240 V, 200 kW at 380/400 V, 220 kW at 415/440 V, 250 kW at 500 V and 315 kW at 690 V. In AC-1 the conventional free-air thermal current is 600 A at 40°C, 500 A at 55°C and 400 A at 70°C; for DC-1, DC-3 and DC-5 the rating is 600 A at 110 V single-pole, 220 V with three poles in series and 600 V with three poles in series.

Short-circuit protection is gG fuses of 630 A; rated short-time withstand current Icw is 4600 A for 10 s and 1 min, 2500 A for 30 s and 3100 A for 15 min, with maximum breaking capacity of 4000 A at 440 V and 3500 A at 690 V. Rated insulation voltage is 1000 V and rated impulse withstand voltage 8 kV. Mechanical durability is 3 million operations, with maximum switching frequency of 300 cycles per hour in AC-1 and AC-3 and 60 cycles per hour in AC-2/AC-4. Power loss is 32 W per pole in AC-1 and 14 W per pole in AC-3.

Coil data: pull-in 1155 V·A; holding 32.6 V·A (4.8 W) at 50/60 Hz and 4.5 W at DC; operating limits 0.85 to 1.1 × Uc at ambient ≤70°C. Operate times are 45 to 55 ms from de-energization to NC closing, 48 to 58 ms from de-energization to NO opening, 45 to 115 ms from energization to NC opening and 50 to 120 ms from energization to NO closing.

Construction and connection: main circuit bar terminals accept 2×240 mm² copper or aluminium cable, with M10 main pole screws at 35 N·m tightening torque; auxiliary circuits accept 2×0.75 to 2.5 mm² flexible conductors or 2×1 to 4 mm² solid/stranded conductors. Coil terminals are IP20 and main terminals IP00. Dimensions are 186 × 216 × 278 mm and net weight 10.6 kg.

Environmental capability: operating and storage temperature -40 to 70°C (-25 to 50°C with a thermal overload relay mounted alongside), no derating up to 3000 m altitude and 5 g shock resistance to IEC 60068-2-27. The product carries CE, UKCA, cULus and CB approvals plus ABS, BV, CCS, LR, PRS and RINA classification certificates, with customs tariff number 85364900.

II. Specifications

表格

Parameter Value
Model AF400-30-11
Product ID 1SFL577001R9100
EAN 7320500220153
Product Type 3-pole block contactor (AF electronic coil)
Main Contacts 3 NO
Auxiliary Contacts 1 NO + 1 NC
Number of Poles 3P
Rated Operational Voltage (main circuit) 1000 V (IEC); 600 V (UL)
Rated Frequency 50/60 Hz
Conventional Free-air Thermal Current Ith 600 A (40°C, open contactors, IEC 60947-4-1)
Rated Operational Current AC-1 600 A (40°C) / 500 A (55°C) / 400 A (70°C) at 690 V and 1000 V
Rated Operational Current AC-3 400 A (220 to 240 V, 380/400 V, 415 V, 440 V, 500 V at 55°C); 350 A (690 V); 155 A (1000 V)
Rated Operational Current DC-1/DC-3/DC-5 600 A (110 V single pole; 220 V three poles in series; 600 V three poles in series, 40°C)
Rated Operational Power AC-3 110 kW (220 to 240 V); 200 kW (380/400 V); 220 kW (415/440 V); 250 kW (500 V); 315 kW (690 V)
Making Capacity AC-3 10 × Ie
Breaking Capacity AC-3 8 × Ie
Short-Circuit Protection gG fuses 630 A
Short-time Withstand Current Icw 4600 A for 10 s / 1 min; 2500 A for 30 s; 3100 A for 15 min (40°C)
Maximum Breaking Capacity 4000 A at 440 V; 3500 A at 690 V
Rated Insulation Voltage Ui 1000 V
Rated Impulse Withstand Voltage Uimp 8 kV (main circuit)
Mechanical Durability 3 million operations
Maximum Switching Frequency AC-1 300 cycles/h; AC-2/AC-4 60 cycles/h; AC-3 300 cycles/h
Power Loss per Pole 32 W in AC-1; 14 W in AC-3
Rated Control Circuit Voltage Uc 100 to 250 V (50 Hz, 60 Hz, DC)
Coil Operating Limits 0.85 to 1.1 × Uc (≤70°C)
Pull-in Consumption 1155 V·A
Holding Consumption 32.6 V·A (4.8 W) at 50/60 Hz; 4.5 W at DC
Operate Time (de-energization) 45 to 55 ms to NC closing; 48 to 58 ms to NO opening
Operate Time (energization) 45 to 115 ms to NC opening; 50 to 120 ms to NO closing
Main Circuit Connection Bar terminals; 2×240 mm² Cu/Al cable; 47 mm² bar
Auxiliary Circuit Connection 2×0.75 to 2.5 mm² flexible; 2×1 to 4 mm² solid/stranded
Terminal Screw / Torque Main poles M10, 35 N·m; control circuit M3.5 / Pozidriv 2
Degree of Protection Coil terminals IP20; main terminals IP00
Dimensions 186 × 216 × 278 mm
Net Weight 10.6 kg
Operating / Storage Temperature -40 to 70°C (-25 to 50°C with thermal overload relay alongside)
Installation Altitude No derating up to 3000 m
Shock Resistance 5 g (IEC 60068-2-27)
Approvals CE, UKCA, cULus, CB, ABS, BV, CCS, CQC, LR, PRS, RINA
UL/CSA General Use Rating 550 A at 600 V and 1000 V AC
UL/CSA Horsepower Rating 125 hp (200 to 208 V); 150 hp (220 to 240 V); 350 hp (440 to 480 V); 400 hp (550 to 600 V)
UL Full Load Amps 358.8 A (200 to 208 V); 360 A (220 to 240 V); 414 A (440 to 480 V); 382 A (550 to 600 V)
Customs Tariff Number 85364900

V. Model Description

Per the ABB AF series naming convention: AF denotes a block contactor using AF technology (electronically controlled coil, wide control voltage range, built-in surge protection); 400 is the rating class (400 A AC-3, 200 kW at 400 V); 30 denotes 3 normally open main poles and 0 normally closed main poles; 11 denotes the pre-mounted auxiliary contacts of 1 NO + 1 NC. The official Product ID is 1SFL577001R9100, the 100-250 V AC/DC coil version; other variants in the family include AF400-30-00 (without auxiliary contacts) and AF400-30-11-70 with a different coil voltage suffix, so the suffix should be checked against the actual control voltage when ordering.

VI. Why Choose Us

  • Professional channel supply, comprehensive model coverage across ABB low-voltage apparatus and industrial automation spare parts
  • Strict quality inspection process ensuring reliable product quality
  • Professional engineering team providing technical support and selection consultation
  • Quick response, efficient logistics, orders accepted
  • Quality assurance, worry-free after-sales service

Q1: What motor size can this contactor drive?

A: In AC-3 it controls a 200 kW motor at 380/400 V (400 A at 55°C), 220 kW at 415/440 V, 250 kW at 500 V and 315 kW at 690 V.

Q2: What is the coil voltage?

A: 100 to 250 V universal, at 50 Hz, 60 Hz or DC, with operating limits of 0.85 to 1.1 × Uc and built-in surge protection.

Q3: How many auxiliary contacts does it have?

A: 1 NO + 1 NC pre-mounted, with 3 NO main poles.

Q4: What short-circuit protection is required?

A: gG fuses of 630 A; Icw is 4600 A for 10 s.