ꄶ Fluid Power
-
ꄶ Test & Measurement
-
ꄶ Analytical Inst.
-
ꄶ Power Transmission
-
ꄶ Electrical
-
ꄶ Automation
-
ꁇ VFDs
-
ꁇ Modules
-
ꁇ Control Systems
-
ꁇ Sensors
-
Proximity Sensors
-
Temperature Sensors
-
Photoelectric Sensors
-
Pressure Sensors
-
Magnetostrictive Sensors
-
Ultrasonic Sensors
-
Load Cells
-
Linear Displacement Sensors
-
Torque Sensors
-
Displacement Sensors
-
Inductive Sensors
-
Vibration Sensors
-
Pulse Sensors
-
Other Sensors
-
Angle Sensors
-
Temperature Digital Indicators
-
Turbidity Sensors
-
Probes
-
-
ꁇ Industrial Computers
-
ꁇ Encoders
-
ꁇ Servo Systems
-
-
ꄶ Thermal
ABB CM-MSS.13S Thermistor Motor Protection Relay (PTC / 1 c/o / 110-130 V AC, 220-240 V AC)
I. Product Overview
The CM-MSS.13S is a thermistor motor protection relay of the CM-MSS range, used to monitor the winding temperature of motors or generators fitted with PTC type A sensors, providing overtemperature, overload and insufficient-cooling protection to the IEC 60947-8 product standard. The sensors are built into the motor windings and their resistance rises with temperature; when it exceeds 2.7 kΩ (±5%) the output relay de-energizes and the red F LED indicates overtemperature, and once the motor has cooled and the resistance falls below 1.2 kΩ (±5%) the relay resets and re-energizes automatically without manual intervention.
This model has a dual control supply: A1-A2 for 220 to 240 V AC and A2-A3 for 110 to 130 V AC at 50/60 Hz, with a voltage tolerance of -15% to +10%; typical current is 24 mA and consumption 3 VA at 110 to 130 V, and 10 mA and 2.2 VA at 220 to 240 V. The supply and measuring circuits are electrically isolated in this model, and power failure buffering is 20 ms.
The sensor circuit is a single channel (T1-T2) for PTC type A sensors to DIN/EN 44081 and DIN/EN 44082, with a maximum cold-state total resistance of <750 Ω for series-connected sensors; maximum sensor circuit current is 3.7 mA and maximum voltage varies with resistance (2.5 V at 1.33 kΩ, 3.7 V at 4 kΩ, 5.5 V open circuit); maximum sensor cable length is 2×100 m at 0.75 mm² or 2×400 m at 2.5 mm². The safety function reaction time is <100 ms, accuracy is 5% within the supply voltage tolerance and 0.5%/K across the temperature range.
The output is one changeover contact (SPDT, terminals 11-12/14) operating on the closed-circuit principle with cadmium-free AgNi alloy contacts; ratings are AC-12 at 230 V 4 A, AC-15 at 230 V 3 A, DC-12 at 24 V 4 A and DC-13 at 24 V 2 A, UL 508 control circuit rating B300 (300 V AC maximum, 5 A continuous, 3600/360 VA making/breaking), general purpose 250 V AC at 4 A. Mechanical lifetime is 30 million operations and electrical lifetime 0.1 million operations at AC-12, 230 V, 4 A; short-circuit protection fuses are 6 A fast-acting for the NC contact and 10 A fast-acting for the NO contact.
The housing is 22.5 mm wide in UL 94 V-0 material with IP50 protection (terminals IP20) and mounts tool-free on IEC/EN 60715 DIN rail in any position (10 mm spacing to adjacent units when switching current exceeds 2 A). Screw-type double-chamber cage terminals accept fine-strand conductors with or without ferrules of 1×0.5 to 2.5 mm² or 2×0.5 to 1.5 mm², and rigid conductors of 1×0.5 to 4 mm² or 2×0.5 to 2.5 mm², with 8 mm stripping length and 0.6 to 0.8 N·m tightening torque. Net dimensions are 22.5 × 85.6 × 103.7 mm and net weight 0.155 kg.
Environment and isolation: operating temperature -25 to +60°C, storage -40 to +85°C; damp heat 6×24 h cycles at 55°C and 95% RH; climatic class 3K5; sinusoidal vibration ±1 mm at 5 to 13.2 Hz and 0.7 g at 13.2 to 100 Hz; shock 10 g for 11 ms. Rated insulation voltage is 300 V AC, rated impulse withstand voltage 4 kV and basic insulation 600 V AC, with protective separation up to 300 V between supply and measuring circuits, pollution degree 3 and overvoltage category III. The relay complies with IEC/EN 60947-5-1 and IEC/EN 60947-8 and with the Low Voltage Directive 2014/35/EU, EMC Directive 2014/30/EU and RoHS Directive 2011/65/EU.
II. Specifications
表格
| Parameter | Value |
|---|---|
| Model | CM-MSS.13S |
| Product ID | 1SVR730700R2100 |
| EAN | 4013614496707 |
| Product Type | Thermistor (PTC) motor protection relay |
| Function | 1 sensor circuit; automatic reset |
| Rated Control Supply Voltage Us | A1-A2: 220 to 240 V AC; A2-A3: 110 to 130 V AC |
| Voltage Tolerance | -15% to +10% |
| Rated Frequency | 50/60 Hz |
| Typical Current / Consumption | 110 to 130 V: 24 mA / 3 VA; 220 to 240 V: 10 mA / 2.2 VA |
| Supply to Measuring Circuit Isolation | Yes |
| Power Failure Buffering | 20 ms |
| Sensor Circuit | T1-T2, 1 channel |
| Sensor Type | PTC type A (DIN/EN 44081, DIN/EN 44082) |
| Cold-state Total Resistance | <750 Ω |
| Trip Resistance (relay de-energizes) | 2.7 kΩ ±5% |
| Reset Resistance (relay energizes) | 1.2 kΩ ±5% |
| Max. Sensor Circuit Voltage | 2.5 V at 1.33 kΩ; 3.7 V at 4 kΩ; 5.5 V open circuit |
| Max. Sensor Circuit Current | 3.7 mA |
| Max. Sensor Cable Length | 2×100 m at 0.75 mm²; 2×400 m at 2.5 mm² |
| Accuracy | 5% within supply voltage tolerance; 0.5%/K across temperature range |
| Safety Function Reaction Time | <100 ms |
| Output Contact | 1 c/o (SPDT), 11-12/14 |
| Operating Principle | Closed-circuit principle |
| Contact Material | AgNi alloy, cadmium-free |
| Minimum Switching Voltage / Current | 24 V / 10 mA |
| Rated Operational Current | AC-12 230 V: 4 A; AC-15 230 V: 3 A; DC-12 24 V: 4 A; DC-13 24 V: 2 A |
| UL 508 Control Circuit Rating | B300 (300 V AC, 5 A continuous, 3600/360 VA) |
| General Purpose Rating | 250 V AC / 4 A |
| Mechanical Lifetime | 30×10⁶ operations |
| Electrical Lifetime | 0.1×10⁶ operations at AC-12, 230 V, 4 A |
| Short-Circuit Protection Fuse | NC contact 6 A fast-acting; NO contact 10 A fast-acting |
| Duty Cycle | 100% |
| Indication | U: green LED (supply); F: red LED (overtemperature) |
| Dimensions | 22.5 × 85.6 × 103.7 mm |
| Net Weight | 0.155 kg |
| Mounting | DIN rail (IEC/EN 60715), tool-free snap-on, any position |
| Minimum Distance | 10 mm when switching current >2 A |
| Housing Material | UL 94 V-0 |
| Degree of Protection | Housing IP50; terminals IP20 |
| Connection Capacity (screw) | Fine-strand 1×0.5 to 2.5 mm² / 2×0.5 to 1.5 mm²; rigid 1×0.5 to 4 mm² / 2×0.5 to 2.5 mm² |
| Stripping Length | 8 mm |
| Tightening Torque | 0.6 to 0.8 N·m |
| Operating Temperature | -25 to +60°C |
| Storage Temperature | -40 to +85°C |
| Damp Heat | 6×24 h at 55°C, 95% RH (IEC/EN 60068-2-30) |
| Climatic Class | 3K5 (IEC/EN 60721-3-3) |
| Vibration | 5 to 13.2 Hz: ±1 mm; 13.2 to 100 Hz: 0.7 g |
| Shock | 10 g / 11 ms |
| Rated Insulation Voltage Ui | 300 V AC |
| Rated Impulse Withstand Voltage Uimp | 4 kV |
| Basic Insulation | 600 V AC |
| Protective Separation | Supply/measuring circuits, up to 300 V (IEC/EN 61140, EN 50178) |
| Pollution Degree / Overvoltage Category | 3 / III |
| Standards | IEC/EN 60947-5-1, IEC/EN 60947-8 |
| Directives | 2014/35/EU (LVD), 2014/30/EU (EMC), 2011/65/EU (RoHS) |
| Immunity | IEC/EN 61000-6-2, IEC/EN 60947-8; ESD Level 3 (6 kV contact / 8 kV air) |
| Emission | IEC/EN 61000-6-3; CISPR 22 / EN 55022 Class B |
| Customs Tariff Number | 85364900 |
V. Model Description
CM-MSS is the thermistor motor protection relay range; the .12 suffix is the 24 V AC/DC single-voltage version and .13 is the dual-voltage version with 110-130 V AC and 220-240 V AC (A1-A2 for 220-240 V, A2-A3 for 110-130 V, with supply and measuring circuits isolated); S denotes screw-type double-chamber cage terminals, while the P version of the same function (CM-MSS.13P, order code 1SVR740700R2100) uses tool-free push-in terminals. Both terminal types share the same connection geometry and terminal positions, so selection depends on field wiring preference.
VI. Why Choose Us
- Professional channel supply, comprehensive model coverage across ABB monitoring relays and industrial automation spare parts
- Strict quality inspection process ensuring reliable product quality
- Professional engineering team providing technical support and selection consultation
- Quick response, efficient logistics, orders accepted
- Quality assurance, worry-free after-sales service
VII. FAQ
Q1: What does this relay monitor?
A: The resistance of PTC type A thermistors built into motor or generator windings; above 2.7 kΩ it interprets the motor as overheated and de-energizes the output relay.
Q2: Is manual reset required after an overtemperature trip?
A: No, it resets automatically; the relay re-energizes once the resistance falls below 1.2 kΩ.
Q3: How is the control voltage connected?
A: The dual-voltage design uses A1-A2 for 220 to 240 V AC and A2-A3 for 110 to 130 V AC at 50/60 Hz.
Q4: What is the output contact rating?
A: One changeover contact rated 4 A at AC-12/230 V and 3 A at AC-15/230 V, UL 508 rating B300, general purpose 250 V AC at 4 A.