ABB CM-MSS.13S Thermistor Motor Protection Relay (PTC / 1 c/o / 110-130 V AC, 220-240 V AC)

The CM-MSS.13S is a thermistor (PTC) motor protection relay of the CM-MSS range with one sensor circuit, monitoring motor winding temperature on the closed-circuit principle, de-energizing its output relay and signalling a red LED on overtemperature (>2.7 kΩ) and resetting automatically after cooling (<1.2 kΩ); dual control supply of 110-130 V AC and 220-240 V AC, one changeover contact output (250 V / 4 A), 22.5 mm DIN-rail housing and screw-type double-chamber cage terminals.
online consultation

Product Details

I. Product Overview

The CM-MSS.13S is a thermistor motor protection relay of the CM-MSS range, used to monitor the winding temperature of motors or generators fitted with PTC type A sensors, providing overtemperature, overload and insufficient-cooling protection to the IEC 60947-8 product standard. The sensors are built into the motor windings and their resistance rises with temperature; when it exceeds 2.7 kΩ (±5%) the output relay de-energizes and the red F LED indicates overtemperature, and once the motor has cooled and the resistance falls below 1.2 kΩ (±5%) the relay resets and re-energizes automatically without manual intervention.

This model has a dual control supply: A1-A2 for 220 to 240 V AC and A2-A3 for 110 to 130 V AC at 50/60 Hz, with a voltage tolerance of -15% to +10%; typical current is 24 mA and consumption 3 VA at 110 to 130 V, and 10 mA and 2.2 VA at 220 to 240 V. The supply and measuring circuits are electrically isolated in this model, and power failure buffering is 20 ms.

The sensor circuit is a single channel (T1-T2) for PTC type A sensors to DIN/EN 44081 and DIN/EN 44082, with a maximum cold-state total resistance of <750 Ω for series-connected sensors; maximum sensor circuit current is 3.7 mA and maximum voltage varies with resistance (2.5 V at 1.33 kΩ, 3.7 V at 4 kΩ, 5.5 V open circuit); maximum sensor cable length is 2×100 m at 0.75 mm² or 2×400 m at 2.5 mm². The safety function reaction time is <100 ms, accuracy is 5% within the supply voltage tolerance and 0.5%/K across the temperature range.

The output is one changeover contact (SPDT, terminals 11-12/14) operating on the closed-circuit principle with cadmium-free AgNi alloy contacts; ratings are AC-12 at 230 V 4 A, AC-15 at 230 V 3 A, DC-12 at 24 V 4 A and DC-13 at 24 V 2 A, UL 508 control circuit rating B300 (300 V AC maximum, 5 A continuous, 3600/360 VA making/breaking), general purpose 250 V AC at 4 A. Mechanical lifetime is 30 million operations and electrical lifetime 0.1 million operations at AC-12, 230 V, 4 A; short-circuit protection fuses are 6 A fast-acting for the NC contact and 10 A fast-acting for the NO contact.

The housing is 22.5 mm wide in UL 94 V-0 material with IP50 protection (terminals IP20) and mounts tool-free on IEC/EN 60715 DIN rail in any position (10 mm spacing to adjacent units when switching current exceeds 2 A). Screw-type double-chamber cage terminals accept fine-strand conductors with or without ferrules of 1×0.5 to 2.5 mm² or 2×0.5 to 1.5 mm², and rigid conductors of 1×0.5 to 4 mm² or 2×0.5 to 2.5 mm², with 8 mm stripping length and 0.6 to 0.8 N·m tightening torque. Net dimensions are 22.5 × 85.6 × 103.7 mm and net weight 0.155 kg.

Environment and isolation: operating temperature -25 to +60°C, storage -40 to +85°C; damp heat 6×24 h cycles at 55°C and 95% RH; climatic class 3K5; sinusoidal vibration ±1 mm at 5 to 13.2 Hz and 0.7 g at 13.2 to 100 Hz; shock 10 g for 11 ms. Rated insulation voltage is 300 V AC, rated impulse withstand voltage 4 kV and basic insulation 600 V AC, with protective separation up to 300 V between supply and measuring circuits, pollution degree 3 and overvoltage category III. The relay complies with IEC/EN 60947-5-1 and IEC/EN 60947-8 and with the Low Voltage Directive 2014/35/EU, EMC Directive 2014/30/EU and RoHS Directive 2011/65/EU.

II. Specifications

表格

Parameter Value
Model CM-MSS.13S
Product ID 1SVR730700R2100
EAN 4013614496707
Product Type Thermistor (PTC) motor protection relay
Function 1 sensor circuit; automatic reset
Rated Control Supply Voltage Us A1-A2: 220 to 240 V AC; A2-A3: 110 to 130 V AC
Voltage Tolerance -15% to +10%
Rated Frequency 50/60 Hz
Typical Current / Consumption 110 to 130 V: 24 mA / 3 VA; 220 to 240 V: 10 mA / 2.2 VA
Supply to Measuring Circuit Isolation Yes
Power Failure Buffering 20 ms
Sensor Circuit T1-T2, 1 channel
Sensor Type PTC type A (DIN/EN 44081, DIN/EN 44082)
Cold-state Total Resistance <750 Ω
Trip Resistance (relay de-energizes) 2.7 kΩ ±5%
Reset Resistance (relay energizes) 1.2 kΩ ±5%
Max. Sensor Circuit Voltage 2.5 V at 1.33 kΩ; 3.7 V at 4 kΩ; 5.5 V open circuit
Max. Sensor Circuit Current 3.7 mA
Max. Sensor Cable Length 2×100 m at 0.75 mm²; 2×400 m at 2.5 mm²
Accuracy 5% within supply voltage tolerance; 0.5%/K across temperature range
Safety Function Reaction Time <100 ms
Output Contact 1 c/o (SPDT), 11-12/14
Operating Principle Closed-circuit principle
Contact Material AgNi alloy, cadmium-free
Minimum Switching Voltage / Current 24 V / 10 mA
Rated Operational Current AC-12 230 V: 4 A; AC-15 230 V: 3 A; DC-12 24 V: 4 A; DC-13 24 V: 2 A
UL 508 Control Circuit Rating B300 (300 V AC, 5 A continuous, 3600/360 VA)
General Purpose Rating 250 V AC / 4 A
Mechanical Lifetime 30×10⁶ operations
Electrical Lifetime 0.1×10⁶ operations at AC-12, 230 V, 4 A
Short-Circuit Protection Fuse NC contact 6 A fast-acting; NO contact 10 A fast-acting
Duty Cycle 100%
Indication U: green LED (supply); F: red LED (overtemperature)
Dimensions 22.5 × 85.6 × 103.7 mm
Net Weight 0.155 kg
Mounting DIN rail (IEC/EN 60715), tool-free snap-on, any position
Minimum Distance 10 mm when switching current >2 A
Housing Material UL 94 V-0
Degree of Protection Housing IP50; terminals IP20
Connection Capacity (screw) Fine-strand 1×0.5 to 2.5 mm² / 2×0.5 to 1.5 mm²; rigid 1×0.5 to 4 mm² / 2×0.5 to 2.5 mm²
Stripping Length 8 mm
Tightening Torque 0.6 to 0.8 N·m
Operating Temperature -25 to +60°C
Storage Temperature -40 to +85°C
Damp Heat 6×24 h at 55°C, 95% RH (IEC/EN 60068-2-30)
Climatic Class 3K5 (IEC/EN 60721-3-3)
Vibration 5 to 13.2 Hz: ±1 mm; 13.2 to 100 Hz: 0.7 g
Shock 10 g / 11 ms
Rated Insulation Voltage Ui 300 V AC
Rated Impulse Withstand Voltage Uimp 4 kV
Basic Insulation 600 V AC
Protective Separation Supply/measuring circuits, up to 300 V (IEC/EN 61140, EN 50178)
Pollution Degree / Overvoltage Category 3 / III
Standards IEC/EN 60947-5-1, IEC/EN 60947-8
Directives 2014/35/EU (LVD), 2014/30/EU (EMC), 2011/65/EU (RoHS)
Immunity IEC/EN 61000-6-2, IEC/EN 60947-8; ESD Level 3 (6 kV contact / 8 kV air)
Emission IEC/EN 61000-6-3; CISPR 22 / EN 55022 Class B
Customs Tariff Number 85364900

V. Model Description

CM-MSS is the thermistor motor protection relay range; the .12 suffix is the 24 V AC/DC single-voltage version and .13 is the dual-voltage version with 110-130 V AC and 220-240 V AC (A1-A2 for 220-240 V, A2-A3 for 110-130 V, with supply and measuring circuits isolated); S denotes screw-type double-chamber cage terminals, while the P version of the same function (CM-MSS.13P, order code 1SVR740700R2100) uses tool-free push-in terminals. Both terminal types share the same connection geometry and terminal positions, so selection depends on field wiring preference.

VI. Why Choose Us

  • Professional channel supply, comprehensive model coverage across ABB monitoring relays and industrial automation spare parts
  • Strict quality inspection process ensuring reliable product quality
  • Professional engineering team providing technical support and selection consultation
  • Quick response, efficient logistics, orders accepted
  • Quality assurance, worry-free after-sales service

VII. FAQ

Q1: What does this relay monitor?

A: The resistance of PTC type A thermistors built into motor or generator windings; above 2.7 kΩ it interprets the motor as overheated and de-energizes the output relay.

Q2: Is manual reset required after an overtemperature trip?

A: No, it resets automatically; the relay re-energizes once the resistance falls below 1.2 kΩ.

Q3: How is the control voltage connected?

A: The dual-voltage design uses A1-A2 for 220 to 240 V AC and A2-A3 for 110 to 130 V AC at 50/60 Hz.

Q4: What is the output contact rating?

A: One changeover contact rated 4 A at AC-12/230 V and 3 A at AC-15/230 V, UL 508 rating B300, general purpose 250 V AC at 4 A.