ifm PM1689 Flush Pressure Sensor (Hygienic / -5 to 100 mbar / 4-20 mA + IO-Link)

The PM1689 is a hygienic flush pressure sensor with a ceramic capacitive measuring element and a flush stainless steel diaphragm, covering -0.005 to 0.1 bar (-5 to 100 mbar), with a G1 external thread sealing cone process connection, media temperature -25 to 150°C and resistance to high-pressure cleaning with aggressive cleaning agents; its outputs are an adjustable 4 to 20 mA analog signal plus IO-Link (COM2), on an 18 to 30 VDC supply in a stainless steel housing rated IP67/IP68/IP69K for the
online consultation

Product Details

I. Product Overview

The PM1689 is a flush pressure sensor for hygienic applications in the food and beverage industry, product designation PM-10BREA01-E-ZVG/US. The sensing element is a ceramic capacitive pressure measuring cell, and the wetted parts are stainless steel (1.4435 / 316L with surface Ra <0.4 μm and Rz = 4 μm), ceramics (99.9% Al₂O₃) and PTFE; combined with the flush diaphragm design it suits viscous media or liquids containing particles as well as liquid and gaseous media, allows flush mounting and withstands high-pressure cleaning with aggressive cleaning agents.

The measuring range is -0.005 to 0.1 bar (-5 to 100 mbar / -0.073 to 1.45 psi) and the measurement is relative (gauge) pressure; vacuum resistance is -1000 mbar, overload pressure 4000 mbar (400 kPa), minimum burst pressure 30000 mbar (3000 kPa), and the maximum permissible operating pressure for CRN applications is 4 bar. The media temperature range is -25 to 150°C.

The sensor provides two outputs: one analog output (4 to 20 mA, adjustable span, maximum load 700 Ω at Ub = 24 V, (Ub-9 V)/21.5 mA) and one digital output (IO-Link, configurable), with short-circuit and overload protection. The analog measuring start point is settable from -5 to 80 mbar and the end point from 15 to 100 mbar in 0.05 mbar steps, with a factory setting of ASP = 0.0 mbar; analog damping (dAA) is 0 to 4 s and the step response time is 30 ms in 2-wire and 7 ms in 3-wire operation.

Accuracy: repeatability <±0.1% (temperature fluctuation <10 K, turn down 1:1), characteristics deviation <±0.5% (linearity including hysteresis and repeatability, limit setting to DIN EN IEC 62828-1), linearity deviation <±0.25%, hysteresis deviation <±0.2% and long-term stability <±0.1% per year (turn down 1:1); the total deviation across the temperature range is ±0.15%/10 K from -25 to 15°C and ±0.2%/10 K from 80 to 150°C.

Communication is IO-Link: transfer type COM2 (38.4 kBaud), IO-Link revision 1.1 to IEC 61131-9, Smart Sensor Profile 3.1 (Measuring Sensor / Common I&D), no SIO mode, A-type master port required, minimum cycle time 3.2 ms and pressure resolution 0.02 mbar; cyclic process data comprises 16 bits of pressure plus 4 bits of device status, acyclic data supports application-specific tags and internal temperature, and the default DeviceID is 670.

Electrical and environmental data: operating voltage 18 to 30 VDC, minimum insulation resistance 100 MΩ (500 V DC), protection class III, reverse polarity protection and integrated watchdog; current consumption is 3.5 to 21.5 mA with a 1 s switch-on delay in 2-wire operation and <45 mA with a 0.5 s delay in 3-wire operation. Ambient temperature is -25 to 80°C and storage temperature -40 to 100°C, with housing protection IP67 / IP68 / IP69K; EMC to DIN EN 61000-6-2 and DIN EN 61000-6-3, shock resistance 50 g (11 ms, DIN EN 60068-2-27), vibration resistance 20 g (10 to 2000 Hz, DIN EN 60068-2-6) and MTTF of 323 years.

Mechanically, the cylindrical housing is stainless steel (1.4404 / 316L) with PBT, measuring Ø30.2 mm and 122 mm long at 337.4 g; the process connection is a G1 external thread sealing cone (-27 mm) with a sealing ring groove to DIN EN ISO 1179-2, tightening torque 20 N·m and switching cycles of 100 million; the electrical connection is one M12 connector (A-coded, 4 gold-plated contacts).

Approvals include 3-A, ACS, CE, CRN, cULus (UL file J022), EC 1935/2004, FCM CN, FCM JP, FDA, Hygienic Cleanable, IO-Link, NSF Reg31 and UKCA.

II. Specifications

表格

Parameter Value
Model PM1689
Product Designation PM-10BREA01-E-ZVG/US
Product Type Flush pressure sensor (hygienic)
Measuring Element Ceramic capacitive pressure measuring cell
Pressure Type Relative (gauge) pressure
Measuring Range -0.005 to 0.1 bar / -5 to 100 mbar / -0.073 to 1.45 psi
Start Point Setting Range -5 to 80 mbar
End Point Setting Range 15 to 100 mbar
Setting Increment 0.05 mbar
Factory Setting (ASP) 0.0 mbar
Vacuum Resistance -1000 mbar
Overload Pressure 4000 mbar / 400 kPa
Minimum Burst Pressure 30000 mbar / 3000 kPa
Max. Permissible Operating Pressure (CRN) 4 bar
Media Temperature -25 to 150°C
Media Viscous or particle-containing liquids; liquids and gases
Flush Mounting Yes
Operating Voltage 18 to 30 V DC
Minimum Insulation Resistance 100 MΩ (500 V DC)
Protection Class (electrical) III
Reverse Polarity Protection / Watchdog Yes / Yes
Current Consumption (2-wire / 3-wire) 3.5 to 21.5 mA / <45 mA
Switch-on Delay (2-wire / 3-wire) 1 s / 0.5 s
Number of Outputs 2
Output Signals Analog; IO-Link (configurable)
Analog Current Output 4 to 20 mA (adjustable span)
Max. Analog Load 700 Ω (Ub = 24 V; (Ub-9 V)/21.5 mA)
Short-Circuit / Overload Protection Yes / Yes
Analog Damping (dAA) 0 to 4 s
Step Response Time (analog) 2-wire: 30 ms; 3-wire: 7 ms
Repeatability <±0.1% (temperature fluctuation <10 K, turn down 1:1)
Characteristics Deviation <±0.5% (linearity incl. hysteresis and repeatability, DIN EN IEC 62828-1)
Linearity Deviation <±0.25% (turn down 1:1)
Hysteresis Deviation <±0.2% (turn down 1:1)
Long-term Stability <±0.1% per year (turn down 1:1)
Total Temperature Deviation -25 to 15°C: ±0.15%/10 K; 80 to 150°C: ±0.2%/10 K
Communication Interface IO-Link
Transfer Type COM2 (38.4 kBaud)
IO-Link Revision 1.1 (IEC 61131-9)
Smart Sensor Profile SSP 3.1 (Measuring Sensor / Common I&D)
SIO Mode No
Master Port Type A
Analog Process Data 3
Minimum Cycle Time 3.2 ms
IO-Link Pressure Resolution 0.02 mbar
Cyclic Process Data Pressure 16 bits; device status 4 bits
Default DeviceID 670
Ambient Temperature -25 to 80°C
Storage Temperature -40 to 100°C
Housing Protection IP67 / IP68 / IP69K
Shock Resistance 50 g (11 ms, DIN EN 60068-2-27)
Vibration Resistance 20 g (10 to 2000 Hz, DIN EN 60068-2-6)
MTTF 323 years
Housing Material Stainless steel (1.4404 / 316L); PBT
Wetted Materials Ceramics (99.9% Al₂O₃); stainless steel (1.4435 / 316L, Ra <0.4 μm / Rz = 4 μm); PTFE
Dimensions Ø30.2 mm, length 122 mm
Weight 337.4 g
Process Connection G1 external thread, sealing cone -27 mm
Sealing Ring Groove DIN EN ISO 1179-2
Tightening Torque 20 N·m
Switching Cycles 100 million
Electrical Connection 1 × M12 connector, A-coded, 4 gold-plated contacts
Pack Unit 1 piece
Approvals 3-A, ACS, CE, CRN, cULus (J022), EC 1935/2004, FCM CN, FCM JP, FDA, Hygienic Cleanable, IO-Link, NSF Reg31, UKCA

V. Model Description

The PM1689 belongs to the PM range of flush pressure sensors, product designation PM-10BREA01-E-ZVG/US: the range is characterised by a flush diaphragm and hygienic design, with measuring range differentiated by the suffix. Other models in the range cover different pressure ranges and process connection forms; selection should match the required range (this model -5 to 100 mbar), process connection (this model G1 external thread sealing cone) and output type (analog plus IO-Link) to the corresponding model and order code.

VI. Why Choose Us

  • Professional channel supply covering ifm sensors and industrial automation spare parts
  • Strict quality inspection process ensuring reliable product quality
  • Professional engineering team providing technical support and selection consultation
  • Quick response, efficient logistics, orders accepted
  • Quality assurance, worry-free after-sales service

VII. FAQ

Q1: What is the measuring range?

A: -0.005 to 0.1 bar, i.e. -5 to 100 mbar, measured as relative (gauge) pressure.

Q2: Which output types are available?

A: One adjustable 4 to 20 mA analog output plus one IO-Link output (COM2, configurable), two outputs in total, with short-circuit and overload protection.

Q3: Which media and applications suit it?

A: The hygienic flush design suits viscous media, particle-containing liquids and liquids and gases in the food and beverage industry, withstands high-pressure cleaning with aggressive cleaning agents, and accepts media temperatures of -25 to 150°C.

Q4: What are the protection rating and connections?

A: Housing IP67 / IP68 / IP69K; process connection G1 external thread sealing cone, electrical connection M12 A-coded 4 gold-plated contacts.