GEORGIN RDN211002 Intrinsically Safe Switching Amplifier (2 Channels / Relay Output / 24-48 VDC)
I. Product Overview
The RDN211002 is an intrinsically safe switching amplifier of the GEORGIN RDN series, an associated intrinsically safe apparatus (safety barrier) installed in the safe area that transmits binary signals from the hazardous area into the safe area. The input accepts a voltage-free contact or a 2-wire proximity sensor to the NAMUR standard; the output provides one relay contact (SPST) per channel, which can be used directly in safe-area control circuits. The device uses galvanic isolation between input, output and supply, with a dielectric strength of 2500 VAC at 50 Hz.
This model has a two-channel configuration and is supplied from 24 to 48 VDC (±10%) with a consumption of no more than 4.5 VA or 1.6 W. The relay output contacts are rated 250 V, 5 A, 100 VA maximum; relay response time is no more than 20 ms and the maximum switching frequency is 10 Hz. A green LED on the front indicates supply present and a red LED indicates that the corresponding output relay is energized. Front-face switches allow the input type and function to be programmed (contact or proximity sensor input, direct repeat, and other functions).
For safety, the device supervises the proximity sensor or resistance-bridge contact input for line break and short circuit: if the sensor circuit is broken or shorted, the output relays are de-energized. Intrinsically safe parameters (RDN2 series, O code) are Uo 12 V, Io 25 mA, Po 0.15 W, with permissible external capacitance of 1410 nF (group IIC) and 9000 nF (group IIB), and external inductance of 45 mH (IIC) and 135 mH (IIB). If the relay contacts are used in a non-intrinsically safe circuit, the circuit switched in normal operation must not exceed 5 A (rms), 250 V (rms) and 100 VA.
Explosion protection and approvals: the protection concept is associated intrinsically safe apparatus, marked II (1) G/D [Ex ia] IIC (or [Ex ia] I), CE 0081; EC type examination certificate LCIE 02 ATEX 6104X (including variations, maximum ambient temperature +60°C for R types); IECEx certificate LCI 09.0013X. Functional safety level SIL 2 to IEC 61508. EMC to EN 61326 and IEC 61000-6-2; low voltage directive to IEC 61010-1, overvoltage category II.
Construction and mounting: ABS housing, weight 200 g, plug-in spring (cage clamp) terminals, mounted on EN 50022 standard rail. Operating temperature -10 to +60°C, storage temperature -25 to +70°C, relative humidity 5% to 95% without condensation.
II. Specifications
表格
| Parameter | Value |
|---|---|
| Model | RDN211002 |
| Product Type | Intrinsically safe switching amplifier (associated IS apparatus) |
| Number of Channels | 2 |
| Input Signal | Voltage-free contact or 2-wire NAMUR proximity sensor |
| Output (per channel) | 1 relay (SPST) |
| Relay Contact Rating | 250 V / 5 A / 100 VA max |
| Response Time (relay) | ≤ 20 ms |
| Max. Switching Frequency (relay) | 10 Hz |
| Supply Voltage | 24 to 48 VDC ±10% |
| Power Consumption | ≤ 4.5 VA or 1.6 W |
| Isolation (input/output/supply) | 2500 VAC, 50 Hz |
| IS Parameters Uo / Io / Po | 12 V / 25 mA / 0.15 W |
| Permissible External Capacitance (IIC / IIB) | 1410 nF / 9000 nF |
| Permissible External Inductance (IIC / IIB) | 45 mH / 135 mH |
| Line Break / Short Circuit Detection | Yes (relays de-energize on fault) |
| Indicators | Green: supply present; Red: output relay energized |
| Housing Material | ABS |
| Weight | 200 g |
| Connection | Plug-in spring (cage clamp) terminals |
| Mounting | EN 50022 standard rail |
| Operating Temperature | -10 to +60°C |
| Storage Temperature | -25 to +70°C |
| Relative Humidity | 5% to 95% (non-condensing) |
| Explosion Protection Marking | II (1) G/D [Ex ia] IIC (or [Ex ia] I) |
| ATEX Certificate | LCIE 02 ATEX 6104X (CE 0081) |
| IECEx Certificate | LCI 09.0013X |
| Functional Safety | SIL 2 (IEC 61508) |
| EMC | EN 61326, IEC 61000-6-2 |
| Low Voltage Directive | IEC 61010-1, overvoltage category II |
V. Model Description
The RDN211002 belongs to the RDN series of intrinsically safe switching amplifiers, where RDN2 designates a two-channel version (RDN1 is single-channel). This model has relay outputs with a 24 to 48 VDC supply; the family also includes transistor-output versions such as the RDN210002 (one transistor per channel, VCE max 65 V, Ic max 100 mA, P max 500 mW) as well as 110 VAC and 230 VAC supply versions, selected at ordering by channel count, output type and supply voltage. Further variants include an alarm output and a signal duplicator (1 input, 2 outputs).
VI. Why Choose Us
- Professional channel supply covering GEORGIN process instruments and explosion-proof interface products
- Strict quality inspection process ensuring reliable product quality
- Professional engineering team providing technical support and selection consultation
- Quick response, efficient logistics, orders accepted
- Quality assurance, worry-free after-sales service
VII. FAQ
Q1: What does this product do?
A: It is an intrinsically safe switching amplifier that galvanically isolates switch signals from contacts or NAMUR proximity sensors in the hazardous area into the safe area, with relay contact outputs.
Q2: What is the output contact rating?
A: 250 V, 5 A, 100 VA maximum, one SPST relay per channel.
Q3: What is the supply voltage?
A: 24 to 48 VDC ±10%, with a consumption of no more than 4.5 VA or 1.6 W.
Q4: What are the explosion protection and functional safety ratings?
A: Explosion protection marking II (1) G/D [Ex ia] IIC under certificate LCIE 02 ATEX 6104X, functional safety SIL 2 to IEC 61508.