GE IC695PSA040K PACSystems RX3i Universal Backplane Power Supply (40 W / 120-240 VAC or 125 VDC)

This unit is a 40 W universal backplane power supply for the PACSystems RX3i series, accepting 120/240 VAC or 125 VDC nominal input (85-264 VAC / 100-300 VDC range) and providing +5.1 VDC, +3.3 VDC and a +24 VDC relay output with 40 W total output, 70 W maximum full-load input, 1500 VAC one-minute isolation and two slots on a universal backplane, powering RX3i controllers and I/O modules.
online consultation

Product Details

I. Product Overview

This product is a 40 W universal backplane power supply for PACSystems RX3i, operating from an input source in the range of 85 to 264 VAC or 100 to 300 VDC with a nominal rating of 120/240 VAC or 125 VDC, and supplying regulated DC power to RX3i system modules. The module provides three outputs: a +5.1 VDC output, a +24 VDC relay output that can power circuits on output relay modules, and a +3.3 VDC output used internally by RX3i modules with IC695 catalog numbers.

Four LEDs on the front of the module indicate status: POWER (green when power is supplied to the backplane, amber when power is applied but the module switch is off), P/S FAULT (red when the supply has failed and no longer supplies sufficient voltage to the backplane), OVERTEMP (amber when near or above maximum operating temperature) and OVERLOAD (amber when at least one output is near or above its maximum output capability). If overtemperature, overload or power supply fault occurs, the CPU fault table records the corresponding fault. An ON/OFF switch behind the front door controls the supply outputs but does not interrupt line power.

For protection, the 5.1 VDC output is electronically limited to 7 A and the 3.3 VDC output to 10 A; an overload (including short circuit) is sensed internally and the supply shuts down and continually tries to restart until the overload is removed, while a non-repairable internal fusible link in the input line serves as backup and the supply usually shuts down before the fuse blows. Terminals for +24 V, -24 V, ground and MOV disconnect accept individual 14 to 22 AWG wires, with 6 A per terminal.

Regarding installation limits, only one unit of this model can be installed in a PACSystems RX3i (IC695 catalog number) universal backplane, and it cannot be used with other RX3i power supplies in redundant or increased-capacity modes; version IC695PSA040C and earlier may cause equipment damage if inadvertently installed in the same backplane as another RX3i supply. If the number of modules required exceeds the supply capacity, additional modules must go into expansion or remote backplanes, or supplies supporting increased-capacity mode must be used. Up to 4 PSA040 supplies may be daisy-chained. Isolation is 250 VAC continuous and 1500 VAC for one minute from input to backplane; ripple and noise are 150 mV on all outputs; ride-through time is 20 ms, the period for which valid outputs are maintained after a power source interruption. Maximum input power at full load is 70 W and inrush current is 4 A for 250 ms maximum, given as a guide for sizing the external power source.

Maximum available output power decreases with surrounding air temperature, with full output power available up to at least 32 °C. Products bearing the UL hazardous location marking or ATEX marking are suitable for the relevant hazardous areas, with ATEX marking II 3G Ex nA IIC T3C, 0 °C ≤ Ta ≤ 60 °C.

II. Specifications

表格

Parameter Value
Model IC695PSA040K
Product Type Universal backplane power supply
Series PACSystems RX3i
Nominal Input Voltage 120/240 VAC or 125 VDC
Input Voltage Range 85 to 264 VAC; 100 to 300 VDC
Maximum Input Power (full load) 70 W
Inrush Current 4 A, 250 ms maximum
Output Power 40 W total maximum; 30 W max at 5.1 VDC; 30 W max at 3.3 VDC
Output Voltage 24 VDC: 19.2 to 28.8 VDC; 5.1 VDC: 5.0 to 5.2 VDC; 3.3 VDC: 3.1 to 3.5 VDC
Output Current 24 VDC: 0 to 1.6 A; 5.1 VDC: 0 to 6 A
Overcurrent Protection 5.1 VDC electronically limited to 7 A; 3.3 VDC limited to 10 A
Isolation (input to backplane) 250 VAC continuous; 1500 VAC for 1 minute
Ripple / Noise (all outputs) 150 mV / 150 mV
Ride-through Time 20 ms
Wiring Terminals One 14 to 22 AWG wire per terminal; 6 A per terminal
Daisy-Chained PSA040 Supplies Up to 4
Slots Occupied 2 slots
Compatible Backplane RX3i universal backplane (one such supply per backplane)
Surrounding Air Temperature 0 to 60 °C (ATEX marking 0 °C ≤ Ta ≤ 60 °C)
Status Indication POWER, P/S FAULT, OVERTEMP, OVERLOAD LEDs
Hazardous Area Marking ATEX II 3G Ex nA IIC T3C

V. Model Description

IC695PSA040 is the RX3i universal backplane 40 W power supply with 120/240 VAC or 125 VDC input; the same family includes IC695PSA140 (40 W multi-purpose supply, 120/240 VAC or 125 VDC input), IC695PSD040 (40 W, 24 VDC input), IC695PSD140 (40 W multi-purpose, 24 VDC input), IC695PSD180 (80 W multi-purpose, 24 VDC input), plus IC694PWR330 (30 W, 120/240 VAC or 125 VDC) and IC694PWR331 (30 W, 24 VDC) for serial expansion backplanes. The suffix of this model identifies the module revision, and ordering or replacement should be checked against the complete model number.

VI. Why Choose Us

  • Professional channel supply covering GE PACSystems RX3i controllers and power modules
  • Strict quality inspection process ensuring reliable product quality
  • Professional engineering team providing technical support and selection consultation
  • Quick response, efficient logistics, orders accepted
  • Quality assurance, worry-free after-sales service

VII. FAQ

Q1: What is the input voltage range?

A: Nominal 120/240 VAC or 125 VDC, with an actual range of 85 to 264 VAC or 100 to 300 VDC.

Q2: Which outputs are provided?

A: +5.1 VDC (0 to 6 A), +3.3 VDC for internal use by IC695 modules, and a +24 VDC relay output (0 to 1.6 A), with 40 W total output power.

Q3: How many units fit in one backplane?

A: Only one unit of this model may be installed in a universal backplane, with no redundancy or capacity sharing; up to 4 PSA040 supplies may be daisy-chained.

Q4: What are the operating temperature and hazardous area approvals?

A: Surrounding air temperature 0 to 60 °C; ATEX marking II 3G Ex nA IIC T3C, 0 °C ≤ Ta ≤ 60 °C.