Products

넳 넲

Classification

Company Culture  ꄲ  Analytical Inst.  ꄲ  Gas Analysis Instruments  ꄲ  Emerson R48-2900M0 Rectifier Module (48 V / 2900 W, Material No. 02130664)
ꁆ ꁇ

Emerson R48-2900M0 Rectifier Module (48 V / 2900 W, Material No. 02130664)

This model is a 48 V/2900 W high-frequency switched-mode rectifier module for telecom power systems, type R48-2900M0, material number 02130664, internal type HA415DZ, with 85-290 V single-phase input, 42-58.5 V output at up to 60 A, hot-swap capability and autonomous load sharing, communicating with the monitoring module over CAN bus, for telecom base station and exchange DC power systems.
online consultation

Product Details

I. Product Overview

This product is a high-frequency switched-mode rectifier module for telecom power systems, type R48-2900M0, material number 02130664, internal type HA415DZ, rated 48 V/2900 W output. It is the customer-specific version of the 48 V/2900 W rectifier module, supplied alongside the same-power R48-2900U0 (material no. 02130701) and R48-2900T0 (material no. 02130698) versions for different customer systems, and serves as the core rectifier unit in 48 V DC telecom power systems such as PS48300-3B/2900, PS48600-3B/2900 and PS48200/2900.

The module has single-phase three-wire input (line, neutral, protective earth) with an input range of 85-290 V and a nominal 200-240 V; DC output is adjustable over 42-58.5 V at 0-60 A, delivering 60.5 A at 48 V and 50 A at 58 V, with a maximum output power of 2900 W between 48 V and 58 V. A built-in digital signal processor monitors and controls the module and communicates with the monitoring module over CAN bus, reporting input and output voltage, output current, temperature, current limit and alarms, and accepting on/off, current-limit, voltage and over-voltage reset commands.

The module supports non-destructive hot swap: insertion or removal in a live system produces no spark and damages no terminals, replacement takes under 1 minute and insertion does not disturb system output voltage. Digital autonomous load sharing keeps the sharing error below ±1.5 A within one system (up to 1200 A). Input power limiting applies: full 2900 W is available at 176-290 V, while at 85-176 V the module enters power limiting and at 85 V output falls to 20% of rating. The module also provides temperature power limiting, temperature-dependent fan speed, input under/over-voltage protection, output over-voltage protection (hardware and software), over-temperature protection, PFC under/over-voltage protection, communication failure protection, fan failure protection and output imbalance detection.

II. Specifications

表格

Parameter Value
Type R48-2900M0
Material No. 02130664
Internal Type HA415DZ
Product Name Telecom power rectifier module (48 V/2900 W)
Input Configuration Single-phase three-wire (line, neutral, protective earth)
Input Voltage Range 85–290 Vac
Nominal Input Voltage 200–240 Vac
Max. Non-operating Static Voltage 415 Vac
Input Current <19 A at 2900 W/176 Vac
Start-up Inrush Current <30 A
Input Surge Current <150% of rated steady-state input peak current
Permissible Mains Frequency 45–65 Hz (nominal 50/60 Hz)
Output DC Voltage Range 42–58.5 V (adjustable, ±0.1 V accuracy)
Output DC Current 0–60 A (current limit adjustable 0–60 A)
Rated Output Power 2900 W
Output Characteristic 60.5 A at 48 V; 50 A at 58 V; 60.5 A held below 48 V
Voltage Regulation Accuracy ≤±0.5%
Load Regulation ≤±0.5%
Line Regulation ≤±0.1%
Start-up Overshoot ≤±1%
Efficiency Up to 91.5%
Load Sharing Error <±1.5 A (system up to 1200 A)
Power Factor ≥0.90 at 25–50%; ≥0.98 at 50–100%; ≥0.99 at 100% load
THD ≤5% at 50–100% rated output
Operating Temperature -20 … +45 °C; full 2900 W at -5 … +45 °C, derating above 45 °C
High-temperature Derating 2320 W (54 V/43 A) at 55 °C; 1450 W at 60 °C; 0 at 65 °C
Relative Humidity ≤90% RH
Operating Altitude ≤2000 m (derating above)
Cooling Forced air (fan speed rises with internal temperature)
Noise ≤45 dB(A) at 1 m
Input Under-voltage Protection 80±3 Vac, hysteresis >15 Vac
Input Over-voltage Protection 295±5 Vac, hysteresis >10 Vac
Output Over-voltage Protection Hardware 58.5–60 V; software 56–59 V (settable, default 59 V)
Over-temperature Protection 50% derating at 85 °C; shutdown at 90 °C
Communication CAN bus (to monitoring module)
Safety Standards UL/EN/IEC 60950-2000, NEBS, CE
Dimensions (H×W×D) 132.5 × 88 × 287 mm
Weight ≤3.5 kg

V. Model Description

In R48-2900M0, R48 denotes a 48 V class rectifier module, 2900 denotes a 2900 W rated output, and M0 is the customer version suffix for this power class; the same power module also exists as U0 and T0 versions (material numbers 02130701 and 02130698, internal types HA415HZ and HA415GZ respectively), while this version's internal type is HA415DZ. Ordering and replacement must use the full type including the suffix together with the material number, since different versions carry different material numbers and must not be selected merely as "48 V/2900 W".

VI. Why Choose Us

  • Professional channel supply covering telecom power rectifier modules and monitoring units
  • Strict quality inspection process ensuring reliable product quality
  • Professional engineering team providing technical support and model verification
  • Quick response, efficient logistics, orders accepted
  • Quality assurance, worry-free after-sales service

VII. FAQ

Q1: What are the output power and current?

A: 2900 W rated; 50 A at 58 V, 60.5 A at 48 V, with 60 A maximum output current.

Q2: What is the input voltage range?

A: 85–290 Vac with 200–240 Vac nominal; power limiting starts below 176 V.

Q3: Does it support hot swap and parallel operation?

A: Non-destructive hot swap is supported, and multiple modules share load autonomously with error below ±1.5 A.

Q4: How does it differ from R48-2900U?

A: It is a different customer version of the same power module, with a different material number and internal type (02130664/HA415DZ); verify against the nameplate.